SECTION 8: GAS PIPING

A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be
checked, preferably by the company, to ensure that
the meter is adequate for the rate of gas supply
required.
Installation pipes must be fitted in accordance with
local and national codes. Pipes of smaller size than
the heater inlet gas connection should not be used.

8.1 Connections
Connect the heater to the gas supply ensuring that
the final connections are as follows:

• Gas supply pipe work is run in medium or heavy

gauge tubing in compliance with local and
national codes.

• Meter and service must be large enough to

handle all the burners being installed plus any
other connected load. The gas pipe which feeds
the system must be large enough to supply the
required gas with a maximum pressure drop of
1/2" wc When gas piping is not included in the
layout drawing, contact the local gas supplier.

• An isolating valve and union connection should

be used and fitted into the supply adjacent to the
heater.

• A minimum 1/8" NPT plugged tapping

accessible for test connection must be installed
immediately upstream of the gas supply
connection to the heater.

• For suspended heaters, an approved metal

flexible connection between the isolating valve
and the heater may be used. To reduce
pressure loss, use one pipe size larger than
the heater gas connection.

IMPORTANT - The complete installation must be
purged and tested for gas soundness in accordance
with local and national codes.
Caution: Do not high pressure (in excess of 1/2 psi
[14" wc]) test the gas piping with the burner
connected. Close manual shut-off valve during any
pressure testing equal to or less than 1/2 psi (14"
wc).
Check the pipe and tubing ends for leaks before
placing heating equipment into service. When
checking for gas leaks, use a soap and water
solution; never use an open flame.

Figure 15: Gas Connection

WARNING

Fire Hazard

Connect gas supply according to Figure 15.

Do not use gas supply pipe and electrical
connections to support heater’s weight.

Gas can leak if not installed properly.

Failure to follow these instructions can
result in death, injury or property damage.

Gas Shut-off Valve

Drip Leg

Cap

Union

Connection

Option B:
Medium or Heavy
Gauge Pipe
Gas Connector

Option A:
Stainless Steel
Flexible Gas
Connector

Do not bend flexible

gas connector

sharply.

• Hold gas nipple

securely with pipe
wrench when attaching
the flexible gas
connector.

• Do not twist flexible
gas connector.

• Ensure all

joints are
gas tight.