Roberts Gorden Blackheat UHA-Series 30 User Manual

Page 53

Advertising
background image

SECTION 14: R

EPLACEMENT

P

ARTS

47

14.7 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure
switch for model. The pressure switches are color coded for each pressure setting. Carry out a start-up
after working on or changing a pressure switch. See Page 29, Section 10.

.

14.8 Ignition Control
The control mounts to the heat exchanger plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable
and all other wiring.

14.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced.

MODEL

UHA[X][S] 30

UHA[X][S] 45

UHA[X][S] 60

UHA[X][S] 75

UHA[X][S] 100

UHA[X][S] 125

Pressure Switch
Kit P/N

90439801

90439810

90439802

90439810

90439810

90439803

Color Code

pink

black

yellow

black

black

gray

Set Point in. wc

.23

.35

.32

.35

.35

.41

Pressure Switch
Snap Ring P/N

90439850

90439850

90439850

90439850

90439850

90439850

MODEL

UHA[X][S] 30

UHA[X][S] 45

UHA[X][S] 60

UHA[X][S] 75

UHA[X][S] 100

UHA[X][S] 125

Axial Fan Guard

91901103

91901103

91901102

91901102

91901102

91901102

Axial

Fan

Motor

90600104

90600104 90600105 90600105

90600106 90600106

Axial Fan Blade

90709004

90709003

90709002

90709001

90709001

90709001

Advertising
This manual is related to the following products: