O.A.S. 2007

c

10 HP Pulley Drive Owner’s Manual

22

Open access cover on the overload, then set

the overload amperage dial to match the FLA

amperage of your motor. The FLA value can

be found on your motor nameplate.

Be sure you have the proper voltage available for your Starter’s Power & Control

Circuit (Control circuit controls Contactor Coil in Starter). Coil voltage is/can be

independent from the line voltage that runs your motor. Customers may desire an

alternative Contactor Coil voltage to connect a Starter to a low voltage control circuit.

Most OAS Starters are shipped with 240v coils.

Plug the Start/Stop Push-Button Assembly into keyed receptacle. (As shown below.)

Run power to the starter and from the starter to your motor. See the manufacturer

instructions for more details.

The Power Circuit connected to the Starter should be fed from a dedicated circuit

breaker or disconnect with fuses. Don’t connect any branch circuits to the Mag Starter

Power Circuit. The overcurrent protection (circuit breaker or fuse*) for the Starter

Power Circuit is to be sized per Article 430.32 of the NEC.

*Use time delay fuses rated for motor circuits.