Installation 8, Venting through existing chimney, Basement installation – Osburn Stoves by SB I HYBRID-45 MF User Manual

Page 8

Advertising
background image

A. VERTICALLY WITH NEW CHIMNEY SYSTEM (Refer to Figure 9

& 10 for basement installation)


NOTE: Follow L-Vent chimney manufacturer’s instructions.

OPTION: To achieve a center vertical installation, a 45º elbow and a
clean-out tee can be used to offset the pipe from the exhaust outlet to
the rear center of the stove.

OPTION: Install L-Vent elbow in place of clean-out tee. Locate stove.
Drop plumb bob to center of tee outlet, mark point on ceiling. Install
ceiling support and L-Vent pipe per L-Vent manufacturer’s instructions.

1. Always maintain 3” clearance from combustible materials. When

passing through additional floors or ceilings, always install firestop
spacer.


2. After lining up for hole in roof, cut either around or square hole in

roof, always 3” larger all the way around pipe. Install upper edge
and sides of flashing under roofing materials, nail to the roof along
upper edge. Do not nail lower edge. Seal nail heads with non-
hardening waterproof mastic.


3. Apply non-hardening, waterproof mastic where the storm collar will

meet the vent. Slide storm collar down until it sits on the flashing.
Seal and install cap. Mobile home installations must use a spark
arrester.


B. VERTICALLY INTO EXISTING CHIMNEY SYSTEM

As an alternative, 3” or 4” L-Vent can be run inside existing chimney to
termination(Figure 11). This is the preferred method.

Follow guidelines for equivalent vent length.

BASEMENT INSTALLATION

FOR BASEMENT INSTALLATION

A 4" PIPE IS RECOMMANDED

WALL
STRAP

FOLLOW CHIMNEY OR
VENT MANUFACTURER'S
INSTRUCTIONS

CLEAN OUT
TEE

CLEAN OUT
TEE

VERTICAL ROOF VENT

12" MINIMUM

CLEARANCE
TO ROOF

CLEAN OUT
TEE

FOLLOW CHIMNEY OR
VENT MANUFACTURER'S
INSTRUCTIONS

ATTIC
INSULATION

SHIELD









FIGURE 9

Venting through roof

INSTALLATION

8

FIGURE 11

Venting through

existing chimney

FIGURE 10

Basement installation

Advertising