Logic input

B) Logic Input (for models with RS-485 only)

B) Logic Input (for models with RS-485 only)

B) Logic Input (for models with RS-485 only)

B) Logic Input (for models with RS-485 only)

B) Logic Input (for models with RS-485 only)

This input is used for remote acknowledgement

(reset).

Safety note:
- Do not run logic input wiring with AC power

cables.

- Use an external dry contact capable of

switching 0.5 mA, 5 Vdc.

- The instrument needs 100 ms to recognize a

contact status variation.

- The logic inputs are NOT

NOT

NOT

NOT

NOT isolated from the

measuring input.

Fig.7

6

7

C

NO

OUT 2

Class 1

(Alarm)

1

2

3

NO - OUT 1

C - OUT 1

NC - OUT 1

OUT 1

Class 1

C.1) Relay Outputs

C.1) Relay Outputs

C.1) Relay Outputs

C.1) Relay Outputs

C.1) Relay Outputs

Fig. 8

The OUT 1 contact rating is 3A/250V AC on
resistive load.
The OUT 2 contact rating is 2A/250V AC on
resistive load.
The number of operations is 1 x 10

5

at specified

rating.
NOTES

NOTES

NOTES

NOTES

NOTES 1) To avoid electric shock, connect power

line at the end of the wiring procedure.

2) For power connections use No 16 AWG

or larger wires rated for at last 75 °C.

3) Use cupper conductors only.
4) Don’t run input wires with power cables.

All relay contacts are protected by varistor against
inductive load with inductive component up to 0.5 A.