Owner’s Manual

Quantum Energy Technologies

Document number: QDC0030PD-11 Page 26 of 40


10b.1: First Level: Press SET + UP for 6 Seconds

t10 Compressor start time delay; 1 to 30 min adjustable. Factory setting 10 min.

p10 Interval for compressor start after stop; 3 to 30 min adjustable. Factory setting 10 min.

d10 Interval for over heat auto-reset; 3 to 30 min adjustable. Factory setting 10 min.

E10 The max de-icing time; 5 to 30 min adjustable. Factory setting 10 min.

F45 The interval for de-icing; 10 to 99 min adjustable. Factory setting 45 min.

10b.2: Second Level: Press SET+DOWN for 6 Seconds

A65 Highest water temperature setting; 30 to 65℃ adjustable. Factory setting 65℃.

d05 Temperature difference for heat pump reactivation (H55 - d05=50℃) 5 to 30℃ adjustable.

Factory setting 5℃.

H95 Overheat trip-out temperature; 60 to 98℃ adjustable. Factory setting 95℃.

L70 Overheat reset temperature; 60 to 98 adjustable. Factory setting 70℃.

P85 Liquid Injection activation temperature; 55 to 98℃ adjustable. Factory setting 85℃.

b75 Liquid Injection de activation temperature; 55 to 98℃ adjustable. Factory setting 75℃.

F08 De-ice de activation temperature; 1 to 15℃ adjustable. Factory setting 8℃.

C-5 De-icing temperature setting; -9℃ to -1℃; Factory setting -5℃.

10b.3: Third Level: Press UP+DOWN for 6 Seconds

FXX Start Up model; F00 to F03 adjustable. Factory setting F02.

F00 Following compressor start the Liquid Injection & De Icing valves remain closed.

F01 Following compressor start the Liquid Injection valve opens, 3 seconds later it closes.

F02 Following compressor start the De-Icing valve opens, 3 seconds later it closes.

F03 Following compressor start the Liquid Injection & De Icing valves open, 3 seconds later they

close.

A25 Compressor amperage overload adjustment; 0 to 30 Amps adjustable. Factory setting 25A.

10c: Error Codes

E01 Water temperature sensor open or short circuit. Auto reset.

E02 Compressor temperature sensor open or short circuit. Auto reset.

E03 Evaporator temperature sensor open or short circuit. Auto reset.

E04 Compressor overload protection. Auto reset the first time, manual reset the second time.

E05 Compressor overheat protection (exceeding H95 setting). Auto reset.

E06 Compressor overheat protection (exceeding 105℃). Manual reset.

E08 Ambient temperature sensor open or short circuit (Optional). Auto reset.