A.11: Technical Data For Service Personnel – SIAM Compressors – R134a

Parameters

150-08ACW-134

270 & 340-11AC3-134

340TIH-134

340-17ACW-134

Superheat setting

1.5Turn(F.Close)

3.5 Turns(7 Turns ) F..Open

3.5Turns(7Turns) F.Open

TX valve + orifice size

TI-E 2#

TEN2 # 3(AAE 2MC)

TEN2 # 4

Winding Resistance @20℃

C-R:

2.13Ω, C-S: 3.91Ω C-R:

0.96Ω, C-S: 1.77Ω

Run Capacitor

30μF (+10, -5%) 370 VAC

30μF (+10, -5%) 370 VAC

60μF (+0, -15%) 400 VAC

Rated power supply

220-240VAC, 50Hz

220-240VAC, 50Hz

220-240VAC, 50Hz

Rated circuit breaker

1Φ, 15A

1Φ, 15A

1Φ, 15A

De-ice control setting

On-5℃, Off + 8℃ (Timed De Icing) On - 5℃, Off + 8℃ (Timed De Icing) On-5℃, Off + 8℃ (Timed De Icing)

Liquid injection capillary

Eyre: ID 1.1mm x 1.5m

Eyre: ID 1.1mm x 2.9m

ID 1.1mm x 2m

Liquid injection thermostat

On at 85℃, Off at 75℃

On at 85℃, Off at 75℃

On at 85℃, Off at 75℃

Water temperature setting

55℃/5℃ (Del. ≥60℃) 55℃/5℃ (Del. ≥60℃)

55℃/5℃ (Del. ≥60℃)

Refrigerant charge

1650g

1850g

2650g

Thermal cut-out setting

105℃, manual reset

105℃, manual reset

105℃, manual reset