A.11: Technical Data For Service Personnel – SIAM Compressors – R134a
Parameters
150-08ACW-134
270 & 340-11AC3-134
340TIH-134
340-17ACW-134
Superheat setting
1.5Turn(F.Close)
3.5 Turns(7 Turns ) F..Open
3.5Turns(7Turns) F.Open
TX valve + orifice size
TI-E 2#
TEN2 # 3(AAE 2MC)
TEN2 # 4
Winding Resistance @20℃
C-R:
2.13Ω, C-S: 3.91Ω C-R:
0.96Ω, C-S: 1.77Ω
Run Capacitor
30μF (+10, -5%) 370 VAC
30μF (+10, -5%) 370 VAC
60μF (+0, -15%) 400 VAC
Rated power supply
220-240VAC, 50Hz
220-240VAC, 50Hz
220-240VAC, 50Hz
Rated circuit breaker
1Φ, 15A
1Φ, 15A
1Φ, 15A
De-ice control setting
On-5℃, Off + 8℃ (Timed De Icing) On - 5℃, Off + 8℃ (Timed De Icing) On-5℃, Off + 8℃ (Timed De Icing)
Liquid injection capillary
Eyre: ID 1.1mm x 1.5m
Eyre: ID 1.1mm x 2.9m
ID 1.1mm x 2m
Liquid injection thermostat
On at 85℃, Off at 75℃
On at 85℃, Off at 75℃
On at 85℃, Off at 75℃
Water temperature setting
55℃/5℃ (Del. ≥60℃) 55℃/5℃ (Del. ≥60℃)
55℃/5℃ (Del. ≥60℃)
Refrigerant charge
1650g
1850g
2650g
Thermal cut-out setting
105℃, manual reset
105℃, manual reset
105℃, manual reset