For Vertical Runs - The vent system must be supported
every eight (8) feet (2.4m) above the fireplace flue outlet by
wall brackets (See Figure 19).

To install support brackets for vertical runs:

• Attach wall brackets to the vent pipe and secure the wall

bracket to the framing members with nails or screws.

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.

NOTE: Model DVK-01TRD does not need an exterior
firestop on an exterior combustible wall. The firestop is
built into the cap.

To install firestops for horizontal runs that pass through either
interior or exterior walls:

• Cut a 12” x 12” (305mm X 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 20. 12" x 12" Hole and Vent Pipe

Figure 21. Heat Shield, Interior & Exterior Firestops

VENT PIPE

1" (25.4 mm)

12"

(305mm)

12"

(305mm)

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

3. Install Support Brackets

For Horizontal Runs - The vent system must be supported
every five (5) feet of horizontal run by a horizontal pipe support.

To install support brackets for horizontal runs:

• Place the pipe supports around the vent pipe.

• Nail the pipe supports to the framing members.

Figure 18. Adding Venting Components

2. Continue Adding Vent Components

• Continue adding vent components, locking each succeed-

ing component into place.

• Ensure that each succeeding vent component is secure-

ly fitted and locked into the preceding component in the
vent system.

• 90° elbows may be installed and rotated to any point

around the preceding component’s vertical axis. If an el-
bow does not end up in a locked position with the pre-
ceding component, attach with a minimum of two (2)
sheet metal screws.

Figure 19. Installing Support Brackets

FLUE
OUTLET

1 INCH MIN.
(25.4 mm)

8 FT. (2.4 m)

WALL STUD

WALL BRACKET

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.