Characteristics, Ip 67 modular i/o splitter boxes for fieldbuses, Advantys – Quantum Instruments Splitter Boxes User Manual

Page 46: Distributed i/o, ftm splitter boxes, Environmental characteristics, Bus module characteristics, Fieldbus characteristics

Advertising
background image

46

Characteristics

0

IP 67 modular I/O splitter boxes
for fieldbuses

0

Advantys™

Distributed I/O, FTM splitter boxes

Environmental characteristics

Product certifications

cULus

Temperature

Operation

°C (°F)

0 to + 55 (+ 32... + 131)

Storage

°C (°F)

- 25 to + 70 (-13... + 158)

Degree of protection

IP 67

Altitude

m (ft.)

0 to 2000 (0...6562)

Vibration resistance

Conforming to IEC 68 part 2-6

15 gn

Shock resistance

Conforming to IEC 68-2-27,
test Ea

50 gn, for 11 ms

Resistance to electrostatic
discharge

Conforming to IEC 61000-4-2

kV

Contact: ± 4
Air: ± 8

Resistance to radiated fields

Conforming to IEC 61000-4-3

V/m

10

Immunity to fast transient
currents

Conforming to IEC 61000-4-4

kV

Power supply: ± 2
Signal: ± 2

Surge withstand

Conforming to IEC 61000-4-5

V

Power supply: (symmetrical and asymmetrical) ± 500
Signals: (symmetrical and asymmetrical) ± 1000
Ground/PE: ± 500

Immunity to conducted
disturbance

Conforming to IEC 61000-4-6

V/m

10

Resistance to magnetic
fields, 50 Hz

Conforming to IEC 61000-4-8

A/m

30

Mounting

All positions

Mechanical mounting

Mounting by two M4 screws (tightening torque 1.5 Nm / 13.3 lbf-in)

Bus module characteristics

Bus module type

FTM 1CN10

FTM 1DN10

FTM 1DP10

Bus type

CANopen

DeviceNet

Profibus-DP

Operating voltage

c V

24

Maximum supply current

A

9

Binary rate

125, 250 and 500 kbits/s

12 Mbits/s

Internal consumption of bus module

mA

70

80

Fieldbus characteristics

Bus type

CANopen

DeviceNet

Profibus-DP

Structure

Type

EN 50325
ISO 11898

EN 50325
ISO 11898
CAN, layer 7 DeviceNet

DIN 19245
EN 50170

Access method

Multimaster, priority
information

Master-Slave

Master-Slave,
Multi-Master

Transmission

Binary rate

1 Mbits/s

500 kbits/s

12 Mbits/s

Medium

2 twisted, shielded wires

4 twisted, shielded wires

2 twisted, type A, shielded
wires (RS 485)

Configuration

Maximum number of devices

127

63

32 without repeater
126 with repeaters

Maximum length of bus

At 1 Mbits/s:
- Max. tap-off length: 0.3 m
(0.98 ft.)
- Max. cumulative tap-off
length: 1.5 m (4.9 ft.)

At 500 kbits/s:
- Max. tap-off length: 6 m
(19.7 ft.)
- Max. cumulative tap-off
length: 30 m (98.42 ft.)

Main line:
- 500 m (1640 ft.) without
repeater,

- 3 km (9843 ft.) with
repeater

Tap-off:
6 m (19.7 ft.) max.

Without repeater:
At 12 Mbits/s:
- 100 m (328.1 ft.) max.

At 1.5 Mbits/s:
- 200 m (656.2 ft.) max.

At 500 kbits/s:
- 400 m (1312 ft.) max.

At < 93.75 kbits/s:
- 1.2 km (3937 ft.) max.

Presentation, functions:
pages 36 - 41

Description:
page 43

Connections:
pages 44, 45

References:
pages 48, 49

Dimensions, schemes:
pages 50, 51

Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com