Ip 67 modular i/o splitter boxes for fieldbuses, Characteristics, Advantys – Quantum Instruments Splitter Boxes User Manual

Page 47: Distributed i/o, ftm splitter boxes, Continued), Digital input/output splitter box characteristics, Analog input/output splitter box characteristics

Advertising
background image

47

Characteristics

(continued)

0

IP 67 modular I/O splitter boxes
for fieldbuses

0

Advantys™

Distributed I/O, FTM splitter boxes

Digital input/output splitter box characteristics

Splitter box type

Inputs

Inputs/outputs

Compact

FTM 1DE08Cpp

FTM 1DE16C12

FTM 1DD08Cpp

FTM 1DD16C12

Expandable

FTM 1DE08CppE

FTM 1DE16C12E

FTM 1DD08CppE

FTM 1DD16C12E

Number of inputs/outputs

8 I

16 I

8 I/O

16 I/O

Internal consumption of splitter box

mA

30 (M8)
50 (M12)

50

30 (M8)
50 (M12)

50

Operating voltage

c V

24

Splitter box max. supply current

A

4

Auxiliary supply max. current

A

4 (only
FTM 1DD16C12)

Bus and I/O undervoltage detection

V

< 18

Input characteristics

Number of inputs

8 I

16 I

0...8 I

0...16 I

Conformity to IEC 1131-2

Type 2

Compatibility with 2-wire/3-wire
proximity sensors

Yes

Input values

Nominal voltage

c V

24

Maximum current

mA

200

Sensor power supply

V

18...30

Logic

Positive

Input filtering

ms

1

Channel status indication

By LED (yellow), one LED per input

Protection against reversed polarity

Yes

Output characteristics

Number of outputs

0...8 O

0...16 O

Output type

Transistor

Nominal output values

Voltage

c V

24

Current

A

0.5

Response time

ms

< 0.5

Max. switching cycle

Hz

Resistive: 50
Inductive: 5

Max. lamp load

W

10

Channel status indication

By LED (yellow), one LED per output

Output connection/cable lengths

0.34 mm

2

/ 5 m (#22 AWG / 16.4 ft.) max

0.75 mm

2

/ 10 m (#19 AWG / 32.8 ft.) max

Analog input/output splitter box characteristics

Splitter box type

Inputs

Outputs

Compact

FTM 1AE04C12C

FTM 1AE04C12T

FTM 1AS04C12C

FTM 1AS04C12T

Number of inputs/outputs

4 I

4 I

4 O

4 O

Internal consumption of splitter box

mA

50

Operating voltage

c V

24

Maximum supply current

Splitter box

A

4

Per channel

A

≤ 0.2

≤ 1.6

Bus and I/O undervoltage detection

V

< 18

Input and output characteristics

Type

Differential 300

Ω

Differential 1 M

Ω

≤ 500 Ω

≥ 500 Ω

Current

Measuring range

0 to 20 mA, 4 to
20 mA

c ± 10 V, c 0 to
10 V

0 to 20 mA, 4 to
20 mA

c ± 10 V, c 0 to
10 V

Resolution

Bits

16

15 + Sign

12

11 + Sign

Conversion time

ms

≤ 2/channel

≤ 1/channel

Input filtering

ms

1

Channel status indication

By LED

Output connection/cable lengths

m (ft.)

30 (98.4) max.

Digital and analog splitter boxes diagnostic characteristics

Internal bus and I/O undervoltage detection

V

< 18

Internal bus communication

By LED

Channel and splitter box short-circuit

By LED

Cable breakage

By LED

Presentation, functions:
pages 36 - 41

Description:
page 43

Connections:
pages 44, 45

References:
pages 48, 49

Dimensions, schemes:
pages 50, 51

Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Advertising