Installation – Tricity Bendix SG211X User Manual

Page 22

Advertising
background image

22

Installation

Location of appliance

The appliance must not be installed in a bed-sitting

room of volume less than 20m

3

or in a bathroom or

shower room. It is essential that the appliance is

positioned as in the enclosed figure i.e. shelves, wall

cabinets and cooker hoods must be fitted a

minimum of 690mm directly above the hob and

400mm above the hob when fitted in line with the

outside of the appliance. If the units are intended to

be fitted adjacent to the appliance but less than

400mm above the hob, then a minimum space of

100mm must be maintained between the sides of

the unit and the appliance (see fig).

If fitted next to or between two base units a

minimum space of 1mm must be left between

each unit and the sides of the appliance. The

levelling feet fitted to the appliance will achieve a

nominal height to hob of 900mm+10mm.

The appliance must be installed in accordance

with EN 1116-1995, regarding the depth of the

superior furniture.

690

400

min 600

max 400

min 570

690

less than

400

100

The appliance must be set on a heatproof floor.

The adjustable feet must not be removed.

L.P.G. cookers or ovens MUST NOT be installed
below ground level, i.e. in a basement, or aboard

any boat, yacht or other vessel.

The cooking appliance must be fitted with a

stability chain firmly secured to the wall (see

fig).

Firmly fix

chain to rear

of cooker

Stability hook

Stability chain

Chain to be as short

as possible.

Ventilation

The room containing the cooker should have an air

supply in accordance with B.S. 5440: Part 2:

Current Editions.

The following requirements for ventilation must

be met.

The cooker should not be installed in a bed sitting

room with a volume of less than 20m

3

, if it is

installed in a room of volume less 5m

3

an air vent

of effective area of 110cm

2

is required; if it is

installed in a room of volume between 5m

3

and

10m

3

, an air vent of effective area 50cm

2

is

required, while if the volume exceeds 11m

3

no air

vent is required. However, if the room has a door,

which opens directly to the outside, no air vent is

required even when the volume is between 5m

3

and 11m

3

.

If there are other fuel burning appliances in the

same room, B.S. 5440: Part. 2: Current

Editions should be consulted to determine the

requisite air vent requirements.

Advertising