2 essential pid (pid3), Expanded functions – Toshiba PROSEC T3H User Manual

Page 48

Advertising
background image

46

PROSEC T3H

2. Expanded Functions

2.4.2 Essential PID (PID3)

FUN 156

PID3

Essential PID


Expression

Input

─[ A PID3 B

→

C ]

─ Output

Function

Performs PID (Proportional, Integral, Derivative) control which is a fundamental method of feed-back control.
(Pre-derivative real PID algorithm)
This PID3 instruction has the following features.

•

For derivative action, incomplete derivative is used to suppress interference of high-frequency noise and to
expand the stable application range,

•

Controllability and stability are enhanced in case of limit operation for MV, by using digital PID algorithm
succeeding to benefits of analog PID.

•

Auto, cascade and manual modes are supported in this instruction.

•

Digital filter is available for PV.

•

Direct / reverse operation is selectable.

Execution condition

Input Operation Output

OFF Initialization

OFF

ON

Execute PID every setting interval

ON when

execution


Operand

Name

Device

Register

Con-

Index

X Y S L R Z T. C. I O X

W

Y

W

S

W

L

W

R

W

W T C D F I

W

O

W

I J K

stant

A Top of input

data

√

√

√

√

√

√

√

√

√

√

√

B Top of

parameter

√

√

√

√

√

√

√

√

√

√

√

C Top of

output data

√

√

√

√

√

√

√

√

√

√


Input data

Control parameter

Output data

A Process input value

PVC

B Proportional gain

K

P

C Manipulation value

MV

A+1 A-mode set value

ASV

B+1 Integral time

T

I

C+1 Last error

e

n-1

A+2 C-mode set value

CSV

B+2 Derivative time

T

D

C+2 Last derivative value

D

n-1

A+3 M-mode MV input

MMV

B+3 Dead-band

GP

C+3 Last PV

PV

n-1

A+4 MV tracking input

TMV

B+4 A-mode initial SV

ISV

C+4 Last SV

SV

n-1

A+5 Mode setting

MODE

B+5 Input filter constant

FT

C+5 Integral remainder

Ir

B+6 ASV differential limit

DSV

C+6 Derivative remainder

Dr

B+7 MMV differential limit DMMV

C+7 Internal MV

MV

n

A-mode: Auto mode

B+8 Initial status

STS

C+8 Internal counter

C

C-mode: Cascade mode

B+9 MV upper limit

MH

C+9 Control interval

∆∆∆∆

t

M-mode: Manual mode

B+10 MV lower limit

ML

B+11 MV differential limit

DMV

B+12 Control interval setting

n