4 expanded data transfer (xfer), Expanded functions – Toshiba PROSEC T3H User Manual

Page 58

Advertising
background image

56

PROSEC T3H

2. Expanded Functions

2.4.4 Expanded data transfer (XFER)

FUN 236

XFER

Expanded data transfer


Expression


Input

─[ A XFER B

→

C ]

─ Output

Function

When the input is ON, data block transfer is performed between the source which is indirectly designated by
A and A+1 and the destination which is indirectly designated by C and C+1. The transfer size (number of
words) is designated by B.
The transfer size is 1 to 256 words. (except for writing into EEPROM)
Data transfer between the following objects are available.

•

CPU register

↔

CPU register

•

CPU register

↔

Expanded F register (IC memory card)

•

CPU register

↔

TOSLINE-S20 or TOSLINE-S20LP (here called S20 or S20LP)

•

CPU register

↔

EEPROM (D register)

Execution condition

Input Operation Output

ERF

OFF No

execution

OFF

−

ON Normal

execution

ON

−

When error is occurred (see Note)

ON

Set

Operand

Name

Device

Register

Con-

Index

X Y S L R Z T. C. I O X

W

Y

W

S

W

L

W

R

W

W T C D F I

W

O

W

I J K

stant

A Source

parameter

√

√

√

√

√

√

√

√

√

√

√

B Transfer

size

√

√

√

√

√

√

√

√

√

√

√

C Destination

parameter

√

√

√

√

√

√

√

√

√

√


Source parameter

Transfer size and status

Destination parameter

A

Bank / CH

Type

B

Transfer size

C

Bank / CH

Type

A+1

Leading address

B+1

Status flag

C+1

Leading address

(Scan healthy map)

B+16

Max. 16 words

•

Refer to the following table for contents of each designation.

•

The status flag is created only when the transfer from S20 to Register.