Expanded functions – Toshiba PROSEC T3H User Manual

Page 67

Advertising
background image

User’s Manual

65

2. Expanded Functions




TOSLINE-S20LP


Station No. 3


T3H

T3H

(self-station)

(target-station)


RW100

D1000

RW101

D1001

RW227

D1127


When R0020 is ON, 128 words data starting with RW100 is transferred to D1000 and after of the T3H on
which station No. 3 S20LP is installed.
When the operation is completed, the status is set in RW050 and instruction output comes ON.


Note

•

Keep the input ON until the output comes ON.

•

This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON)
(1) Target station No. is invalid. (for S20LP)
(2) Invalid register designation. (In case of T and C registers, T

→

T and C

→

C is only possible)

(3) Source/destination register address range is out of valid range.
(4) Destination register is write-protected.
(5) Response time-out is occurred.
(6) If expanded F register is designated;

- when MMR setting is not made.

- when IC card is not installed.

- when IC card is used to store program.

- when IC card is write-protected. (for destination)

•

By using SW067, register write-protect is available against SEND instruction of other T3H.

F 9 8 7 6 5 4 3 2 1 0

SW067 SW

C

T

F

D

RW

LW

W

YW


0: Write enable

1: Write protect


•

Resetting the status register (operand B) is necessary at the first scan.

•

When using the TOSLINE-S20LP or Ethernet module (EN311), read the manual for these network
modules.

Both F register in CPU and
expanded F register in IC card