2. Expanded Functions


PID

algorithm:

∆

∆

∆

∆

∆

MV

K

P

I

D

MV

MV

MV

n

n

n

n

n

n

n

P

=

⋅

+

+

=

±

−

(

)

1


Here,

∆

P

e

e

e

SV

PV

n

n

n

n

n

n

=

−

=

−

−

1

∆

∆

I

e

t

Ir

T

n

n

I

=

⋅ +

∆

∆

∆

∆

D

T

PV

PV

t D

Dr

t

T

D

D

D

n

n

n

n

n

n

n

D

D

=

⋅

−

−

⋅

+

+ ⋅

=

+

=

−

−

−

(

)

.

1

1

1

0 1

η

η


Parameter details


A+1

⋅

A

Process input value PVC (0 to 100 %)

Data range: 0.0 to 100.0

A+3

⋅

A+2

Auto mode set value ASV (0 to 100 %)

Data range: 0.0 to 100.0

A+5

⋅

A+4

Cascade mode set value CSV (0 to 100 %)

Data range: 0.0 to 100.0

A+7

⋅

A+6

Manual mode MV MMV (-25 to 125 %)

Data range: -25.0 to 125.0

A+9

⋅

A+8

MV tracking input TMV (-25 to 125 %)

Data range: -25.0 to 125.0

A+11

⋅

A+10

Mode setting MODE

A+11 A+10

F

0 F C 8 4 0

Operation

mode

00 : Manual mode

01 : Auto mode

10 : Cascade mode

11 : (Reserve)


Tracking

designation

0 : No

1 : Yes


B+1

⋅

B

Proportional gain KP (0 to 327.67)

Data range: 0.0 to 327.67

B+3

⋅

B+2

Integral time TI (0 to 32.767 min., stop if TI = 0)

Data range: 0.0 to 32.767

B+5

⋅

B+4

Derivative time TD (0 to 32.767 min.)

Data range: 0.0 to 32.767

B+7

⋅

B+6

Gap (dead-band) GP (0 to 10 %)

Data range: 0.0 to 10.0

B+9

⋅

B+8

Auto mode initial set value ISV (0 to 100 %)

Data range: 0.0 to 100.0

B+11

⋅

B+10

Input filter constant FT (0 to less than 1)

Data range: 0.0 to less than 1.0

B+13

⋅

B+12

ASV differential limit DSV (0 to 100 %/

∆

t)

Data range: 0.0 to 100.0

B+15

⋅

B+14

MMV differential limit DMMV (0 to 100 %/

∆

t)

Data range: 0.0 to 100.0

(If GP

≠

0, Gap is applied)

(If T

I

= 0,

∆

I

n

= 0)

(Fixed)