Evacuation – Toshiba CARRIER RAV-SP420CT-UL User Manual

Page 13

Advertising
background image

– 12 –

Under Ceiling Type

Installation Manual

EN

Toshiba

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the nut

may crack depending on the conditions.

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times)
Therefore, using a torque
wrench, tighten the flare pipe
connecting sections which
connect the indoor and
outdoor units of the specified
tightening torque.
Incorrect connections may
cause not only a gas leak, but
also a trouble of the
refrigeration cycle.
Align the centres of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

• Shape of valve differs according to the outdoor unit.

For details of installation, refer to the Installation
Manual of the outdoor unit.

„

Evacuation

Using a vacuum pump, perform vacuuming from the
charge port of valve of the outdoor unit.
For details, follow to the Installation Manual attached to
the outdoor unit.
• Never use the refrigerant sealed in the outdoor unit

for air purge.

REQUIREMENT

For the tools such as charge hose, etc., use those
manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A”
referring to the attached Installation Manual of outdoor
unit.
Be sure to use a scale to charge the refrigerant of
specified amount.

REQUIREMENT

• Charging an excessive or too little amount of

refrigerant causes a trouble of the compressor.
Be sure to charge the refrigerant of specified
amount.

• A personnel who charged the refrigerant should

write down the pipe length and the added
refrigerant amount in the nameplate attached to the
service panel of the outdoor unit. It is necessary to
troubleshooter the compressor and refrigeration
cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached to
the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas
leaks or not, from the pipe connecting section or cap of
the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC
refrigerant (R410A, R134a, etc.).

(Unit: ft•lbs (N•m))

Outer dia. of copper

pipe

Tightening torque

1/4” (6.4 mm)

10 -13 (14 - 18)

3/8” (9.5 mm)

24 - 31 (33 - 42)

1/2” (12.7 mm)

37 - 46 (50 - 62)

5/8” (15.9 mm)

46 - 57 (63 - 77)

Flare at

indoor

unit side

Flare at

outdoor

unit side

Externally

threaded side

Half union

Flare nut

Internally

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

12-EN

+00EH99864801_00Ta.book Page 12 Tuesday, November 24, 2009 5:40 PM

Advertising