Filter sign setting, Group control – Toshiba CARRIER RAV-SP420CT-UL User Manual

Page 24

Advertising
background image

– 23 –

Under Ceiling Type

Installation Manual

Toshiba

„

Filter sign setting

According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
(

1

2

3

4

5

6

).

• For the CODE No. in Procedure

3

, specify [01].

• For the [SET DATA] in Procedure

4

, select the setup

data of filter sign lighting time from the following
table.

„

To secure better effect of
heating

When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow to the basic operation procedure
(

1

2

3

4

5

6

).

• For the CODE No. in Procedure

3

, specify [06].

• For the SET DATA in Procedure

4

, select the setup

data of shift value of detection temperature to be set
up from the table below.

„

Group control

Group control for system of multiple units

One remote control can control maximum 8 indoor
units as a group.

Group control in single system

• For wiring procedure and wiring method of the

individual line (Identical refrigerant line) system,
follow to “Electric work”.

• Wiring between lines is performed in the following

procedure.
Connect the terminal block (A/B) of the indoor unit
connected with a remote control to the terminal
blocks (A/B) of the indoor units of other indoor units
by wiring the inter-unit wire of the remote control.

• When the power supply has been turned on, the

automatic address setup starts and “

” display

which indicates that address is being set up flashes
on the display part. During setup of automatic
address, the remote control operation is not
accepted.

Required time up to the finish of automatic

addressing is approx. 5 minutes.

NOTE

In some cases, it is necessary to change the address
manually after setup of the automatic address
according to the system configuration of the group
control.

Procedure example 1

Manual address setup procedure
While the operation stops, change the setup.
(Be sure to stop the operation of the unit.)

Setup data

Filter sign lighting time

0000

None

0001

150H

0002

2500H (Factory default)

0003

5000H

0004

10000H

Setup data

Detection temp shift value

0000

No shift

0001

+1.8 °F (+1 °C)

0002

+3.6 °F (+2 °C)

(Factory default)

0003

+5.4 °F (+3 °C)

0004

+7.2 °F (+4 °C)

0005

+9.0 °F (+5 °C)

0006

+10.8 °F (+6 °C)

Outdoor

unit

Outdoor

unit

Outdoor

unit

Outdoor

unit

Outdoor

unit

Indoor

unit

Indoor

unit

Indoor

unit

Indoor

unit

Indoor

unit

Remote

control

Finish of address setup by

power-ON

(Max. 8 units)

23-EN