External Connections




























Figure 6. LF502/LF232*F flowmeter Wiring Diagram


Wiring Precautions

(1) Be sure to use thick walled steel conduit (22

mm) for signal and excitation cable wiring

between the detector and converter. The

conduit screw is R (PT)1/2. Use flexible

conduits at the cable outlets of the detector as

needed.

(2) Make the grounding wire as short as possible.

Do not use a common ground shared with

other equipment where earth current may flow.

An independent

earth

ground

is

recommended.

(3) The meter may affect its accuracy when the

electric potential of measurement fluid is

unstable condition.

• Make the piping of the upstream side and

downstream side the same material.

• When the material of next pipes are conductive

like metal, use a 5.5mm

2

or larger core cable for

grounding of detector and wire it at 2 places as

follows.

• Between Grounding terminal at detector body

and Grounding ring at upstream side.

• Between Grounding terminal at detector body

and Grounding ring at downstream side.

• When the material of next pipes are

non-conductive like plastic, use a 5.5mm

2

or

larger core cable for grounding of detector and

wire 1 place as follows.

• Between Grounding terminal at detector

body and Grounding (100 ohm or less).

(4) DO1 to DO4 and DI1 to DI2 use the same

common terminal (COM). This COM can not

connect to other instruments that have their

own ground terminal (Power supply for

connecting to DI or DO, etc...). Need to wire

separately.

Power supply

Current output (4 to 20mA)

Terminal box

Digital input 1 (opt.)
(20 to 30 Vdc)

Digital input 2 (opt.)

Excitation cable

(3-wire hard-rubber sheathed cable)

Digital output

Digital output 2 (opt.)

Digital output 3 (opt.)

Digital output 4 (opt.)

Ⅳ wire
5.5mm

2

or more

Signal cable
(2-wire shielded hard-rubber sheathed cable)

Output cable
(CVV-S)

Power supply

(CVV)

Digital I/O cable

(CVV-S)

Thick walled steel conduit

Detector

Grounded with 100Ω or
less ground resistance