Connecting the Power Wires

WARNING: All electrical components must meet applicable
national and local electrical codes including installation by
qualified personnel. These codes may require a means in the fixed
wiring of disconnecting AC power having a contact separation of
at least 0.120" (3mm) in the line and neutral poles. The wire used
for connection to the controller must have insulation rated at
105°C minimum. Do not connect the controller to one phase of a
3-phase power source. Ensure the AC power source is OFF prior
to connecting to the controller.

Connecting an Earth Ground Source

Caution: Warranty may be void if the controller is not properly
grounded to an earth ground device.

!

1. Install a copper-clad ground device; i.e., 8’ (2,5m) ground rod into

well moistened soil. The top of the rod buied at least 12” (30,5cm)

below grade.

2. Using a Cad-weld

TM

(or equivalent) attachment method, connect a

6 AWG (10mm

2

) solid copper wire to the ground device and route

to the controller in the most direct path. (Wire bends should be

minimal and not be less than 8” (20,3cm) in radius).

3. Route ground wire through cabinet base using 1/4” (6mm) access

hole provided.

(continued)

Hot
Neutral

Equipment

Ground

.

1. Ensure the power is discon-

nected at the source.

2. Route the AC power and

equipment ground wires

through electrical conduit

to the controller.

3. Remove the wiring access

panel located below the

transformer.

4. Using a small screwdriver,

secure wires as follows:

hot to L, neutral to N, and

equipment ground to

5. Reinstall the cover plate.
6. Apply power to controller.