F3200 Installation & Programming Manual

Document No: LT0122

Applications

Page 9-10

5 July 2001

Issue 2.7

LOGIC & CONFIGURATION (CONTINUED)

Relay 1 = Alert O/P (1st stage sign FIRE ALARM)

Relay 2 = Evac O/P (2nd stage sign EVACUATE and DO NOT ENTER)

Relay 3 = Gas Release Solenoid

Relay 4 = System Inoperative sign

Isolate = Guard Relay (see note 2)

Timer

T1 [S30:0] = V1

30 Second time delay from "Gas Initiated" (second stage).

Variables

V1 = Z1A.Z2A.^Z5A + Z3A

Open Collector LEDs

OC1 = V1

OC2 = Z3A

OC3 = Z4A

OC4 = Z5A + OC5 + Z7A + Z4:7(1)I + Z1:7(1)F + R3F +R1I+R2I +R4I (see notes 2,9)

OC5 = Z6A+Z1:3(1)I + R3I + Guard Iso (if isolatable, see note 2)

Relays

R1 = Z1A + Z2A + Z3A + Z4A

(Alert)

R2 = Z4A + V1

(Evac)

R3 = T1

(Gas Release)

R4 = OC4

(System Inoperative)

ISO (or Rn) = V1

(Guard) (see note 2)

Configure Circuits

AZC

Alarm Text

B1

Circuit 1

Smoke (1)

-

Circuit 2

Smoke (1)

-

Gas Start

MCP/Manual (4)

-

Gas Released

FSW (3) or PSW (6)

Alarm (2)

Gas Inhibit

MCP/Manual (4)

-

Gas Isolated

MCP/Manual (4)

If required (see note 3)

Lock-off Valve

VMD/Valve (5)

If required (see note 9)

(Circuits 1 and 2 use all default settings).

Configure Zones

Zone

Latch MAF Anc1 Anc2 Bells

Circuit 1

-

-

- - -

Circuit 2

- -

- - -

Gas Start

N ? -

- - - (see note 10)

Gas Released

- -

- - -

Gas Inhibit

N N N N N

Gas Isolated

N N N N N If required (see note 3)

Lock-off Valve

N

N

N

N

N If required (see note 9)

(Zones 1-4 use all default settings. Zone 3 may be required to be non-latching. See note 10.)