F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-12

5 July 2001

Issue 2.7

AZC SPECIFICATIONS (CONTINUED)

Timing

Standard Delay

2.3 sec (2.0 - 2.6 sec)

(into Alarm, Fault, Normal)

AZC Reset

5.3 sec (5.0 - 5.6 sec)

AZC Ignore Period 1

2 sec nom (plus std 2.3 sec delay)

(after Reset)

AZC Ignore Period 2

1 sec nom (plus std 2.3 sec delay)

(after Start Up or Programming)

AZC Time Into Alarm

Programmable 0-250 sec

AZC Time Out of Alarm

Programmable 0-250 sec

Refer to Section 7.2.4 for detail on other sequences and programmable delays.

3.4.2 MAF/PSU

INPUTS

Battery Termination

One pair screw terminals; 4sq mm max cable

AC Input

31V rms; 3.6A rms; 2.8mm tab terminals

Door Switch

5V, 0.5mA, Unsupervised, 4 Way .1" pcb header, J6

MCP

5V, 1mA, 2k7 EOLR, 4 Way .1" pcb header, J6

Spare Inputs (not fitted)

5V, 0.5mA, Unsupervised, Cabinet internal use only, 4 Way

.1" pcb header, J5

Relay Supervision

Anc 1 Sup/Anc 2 Sup

One screw terminal each

Modes of Operation

1 Door holder (Default for Anc 1)

2 Load (Default for Anc 2)

Relay Off

Relay On

Door Holder Mode expects

Voltage Present

No Voltage Present

Load mode expects

Resistive to 0V

Open Circuit or Voltage Present

Voltage Threshold

3.65V Nom

(Door Holder Mode)

Supervision Current

0mA @ +5V, 1mA @ 0V

Load Resistance

400 Ohm - 10k Ohm

(Load Mode)

less than 400 Ohm with series diode at load.

14 Ohm absolute minimum.

Bells Relay

Form

Reverse polarity - requires series diode at each device