Document No: LT0122

F3200 Installation & Programming Manual

System Specifications

Issue 2.7

5 July 2001

Page 3-9

AZC SPECIFICATIONS (CONTINUED)

Min

Typ

Max

AZC current limit (note 1)

13.5mA

15.5mA 16.5mA

(14.5mA)

EOL & detector quiescent

11.95mA

EOL, no detectors

7.0mA

7.8mA 8.2mA

(7.2mA)

Fault threshold

4.4mA

5.75mA 6.8mA

Detector quiescent

0mA

4.0mA

Notes

1.

The minimum figures shown are for battery voltage greater than the minimum

Standby (Battery Fail) level i.e. 21.5V. The figures shown in brackets are for a

battery voltage greater than 22.5V.

2.

Modes 1 & 2 have the same thresholds before the Alarm state is latched. For Mode

2 additional current is turned on once the Alarm state is latched (refer to Graph

3.4.2).

Min

Typ

Max

Mode 3 Only

Current into short circuit

34.3mA

Current into 800 Ohm (note 3)

14.2mA

14.8mA 15.3mA

Current into 2000 Ohm (note 4)

8.0mA

8.2mA 8.4mA

EOLR Current

2mA

Minimum current for EOLR & 2k circuit

1.64mA

Modes 3 & 4

Fault thresholds

0.85mA

1.28mA 1.59mA

Maximum allowable load or circuit leakage

0.5mA

Notes

3.

I.e. short at end of an 800 Ohm circuit (gives voltage band B2 alarm, ref graph 3.4.1).

4.

I.e. short at end of a 2000 ohm circuit (gives voltage band B3 alarm, ref graph 3.4.1).

MCP Zener Diode

For voltage band B3 operation

BZT03C15 3W, 15V.