Turbomachinery Package Specification

Taurus

60 Compressor Set and Mechanical Drive

Figure 23. Typical Water Mist Suppression Fire Cylinder Cabinet

Table 11. Enclosure Specifications

Enclosure

Optional Ventilation Fan Motor Voltage Ratings

380 VAC, 400 VAC, and 415 VAC (50 Hz)
460 VAC and 575 VAC (60 Hz)

Primary Enclosure Lighting Voltage

220 VAC (50 Hz) or 110 VAC (60 Hz)

Standby Enclosure Lighting Voltage

120 VDC

Sound Pressure Level

See Note (a)

Enclosure Roof Load

244 kg/m

2

(50 lb/ft

2

)

Enclosure Wind Load

193 kph (120 mph)

Approximate Measurements

Height

2.6 m (8 ft 6 in.), Does Not Include Ventilation Ducting

Width

6.4 m (21 ft), With Enclosure Doors Open and Engine
Removal Hoist Attached

Driver Length

6.1 m (20 ft)

Driven Length (Single Body Compressor)

4 m (13 ft)

Approximate Weights

Gas Turbine Enclosure

3054 kg (6750 lb)

Compressor Enclosure (Single Body)

1656 kg (3660 lb)

Fire Suppression System Compliance

CO

2

Fire Suppression System

U.S. National Fire Protection Association (NFPA) 12
United States Coast Guard (USCG) CFR 46

Water Mist Fire Suppression System

U.S. NFPA Code 750
USCG CFR 46

Water Mist Fire Suppression System

Minimum Operating Temperature

4°C (40°F), Optional Heater Available

CO

2

Fire Cylinder Cabinets

Fire Cylinder Cabinet, Main

Height

213 cm (84 in.)

Width

152 cm (60 in.)

Depth

53 cm (21 in.)

Approximate Cabinet Weight

429 kg (946 lb), Without Cylinders

Approximate Cylinder Weight

45 kg (100 lb)

© 2009 Solar Turbines Incorporated. All rights reserved.