Toshiba VF-AS1 User Manual

Page 4

Advertising
background image

E 6 5 8 1 3 6 4

3

1.1.1. Switching circuit connection diagram, Time chart,

Parameter settings




























Title

Function

Adjustment range

Setting value



Output signal selection of commercial
power/inverter switching

0 to 3

1 (Automatic switching in case

of trip)



*3

Inverter side switching waiting time

0.1 to 10.0 seconds

Different for each model



*3

Commercial power side switching waiting
time

0.37 to 10.0 seconds

0.62



*1

Input terminal selection #6 (S2)

0 to 135

20

(Emergency stop)



Output terminal selection #1 (OUT1)

0 to 119

46

(Commercial power/inverter

switching output 1)



Output terminal selection #2 (OUT2)

0 to 119

48

(Commercial power/inverter

switching output 2)

*1:Be careful about Items 5 and 7 in 1.3, “Precautions.”

*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of 
*3: and  are included the operation time of the relay and the magnet contactor.

In almost all cases, it is not necessary to change these parameter settings.

Setting
frequency

Inverter-side switching wait
time 

*2

Frequency after speed is
detected

Commercial power

switching wait time



Speed detection time

Inverter run

Commercial power run

P24-OUT1(RY1)
for inverter

run

output

P24-OUT2(RY2)
for commercial
power run

output

Run signal

F-CC

Stand-by signal

ST-CC

ON

ON

ON

ON

ON

0Hz

Reset signal

RES-CC

Inverter

trip occurs

ON

Inverter run

Inverter protective
action signal

F L

FLA

FLC

FLX

X

F

OFF

ON

X

MC3

MC2

RY1

(Inverter)

X

MC3

MC1

MC2

RY2

(Commercial

power)

X

Advertising
This manual is related to the following products: