2. Commercial Power Supply/Inverter Switching

The motor runs on commercial power supply under rated operating conditions and when the motor
runs in energy saving mode with its input power frequency lowered, this circuit switches the motor
to the inverter power without stopping the motor.

2.1. Standard connection diagram





































*1: The control power supply backup option (Model: CPS002Z) is needed.
*2: Observe the Item 1 in 2.2, “Precautions.”

*3: See Item 2 in 2.2, “Precautions.”

*4: Be careful about Items 3 in 2.2, “Precautions.”
*5:

Be careful about Items 5 and 7 in 2.2, “Precautions.”

*6:

Be careful about Item 6 in 2.2, “Precautions.

MC1

*2

For motor protection
THR

*4

Motor

FL

G / E

F

RES

CC

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

FLC

FLB

FLA

Run
command

S1

ST

R

S2

S3

OUT2

P24/PLC

OUT1

RY2

PO

PB

PC/-

PA/+

Main circuit

Stand-by

*7

Reset

*6

Emergency
stop

*5

CCA RX VI/II RR/S4 PP

AM

FM

OUT1

MCCB

Common

I M

RY1

Protective action

detection

relay

MC3

*2

MC2

*3

+SU

Control

circuit

Control power supply

backup option

*1

NO

CC

Commercial run
switching signal

*7: VF-AS1's 'WP1/WN1' model and VF-PS1 don't have 'ST'

terminal. Please set next parameter for use 'S3' terminal as
'ST' function.

f110

(Always ON function selection 1)

= 0

f115 (Input terminal function selection: S1) = 6