Toshiba VF-AS1 User Manual

Page 5

Advertising
background image

E 6 5 8 1 3 6 4

4

1.2. Standard connection diagram (Star-delta switching start)

This is the circuit to switch the motor to commercial power supply Star Delta (star-delta) connection
startup when the inverter’s protective function is activated.








FL

G / E

F

RES

CC

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

FLC

FLB

FLA

S1

ST

R

S2

S3

OUT2

P24/PLC

OUT1

RY2

PO

PB

PC/-

PA/+

Main circuit

MCCB

I M

RY1

MC3

*2

MC2

*3

MC1

*2

MCY

MCD

For motor protection
THR

*4

Motor

Run
command

Stand-by

*7

Reset

*6

Emergency
stop

*5

Protective action

detection

relay

Common

+SU

Control

circuit

CCA RX VI/II RR/S4 PP

AM

FM

OUT1

NO

CC

*1: The control power supply backup option (Model: CPS002Z) is needed.
*2: Observe the Item 1 in 1.3, “Precautions.”

*3: See Item 2 in 1.3, “Precautions.”

*4: Be careful about Items 3 in 1.3, “Precautions.”
*5:

Be careful about Items 5 and 7 in 1.3, “Precautions.”

*6:

Be careful about Item 6 in 1.3, “Precautions.

Control power supply

backup option

*1

*7: VF-AS1's 'WP1/WN1' model and VF-PS1 don't have 'ST'

terminal. Please set next parameter for use 'S3' terminal as
'ST' function.

f110

(Always ON function selection 1)

= 0

f117 (Input terminal function selection: S3) = 6