Installer Settings Summary

Setting

Range

Default

Display Lock

Y or N

N

Locks out front buttons

F/C Mode

C or F

F

Screen Timeout

0-240

0

seconds

Schedule Enable

Y or N

N

Max heat setpoint

55F-90F (12C-32C)

90F (32C)

Min cool setpoint

60F-99F(15C-37C)

55F (15C)

Min Run Time (MRT)

1 – 9

3

Min Off Time (MOT)

5 – 9

5

Mechanical - Type

Std or HP

Std

Mechanical - Fan Type

Gas or Elec

Gas

Mechanical - C/O Type

w/Heat or w/Cool

w/Cool

Mechanical - 2nd Stage
Heat

Y or N

N

Mechanical - Aux Heat

Y or N

Y

Mechanical - 2nd Stage
Cool

Y or N

N

Filter Interval

300

Maint Interval

3000

H/C Delta

3 – 15

3

Heat Delta Stage 1 On

1 – 8

1

Heat Delta Stage 1 Off

0 – 8

0

Heat Delta Stage 2 On

1 – 8

2

Heat Delta Stage 2 Off

0 – 8

0

Heat Delta Stage 3 On

1 – 8

3

Heat Delta Stage 3 Off

0 – 8

0

Cool Delta Stage 1 On

1 – 8

1

Cool Delta Stage 1 Off

0 – 8

0

Cool Delta Stage 2 On

1 – 8

2

Cool Delta Stage 2 Off

0 – 8

0

Fan Cycler ON time

0 – 120

0

0 = Fan Cycler OFF

Fan Cycler Off Time

10 – 120

10