Display board, E2futaba vfd display data connection – Viking VCWB300 User Manual

Page 14

Advertising
background image

DIAGNOSTIC CHECK POINTS (con’t)

E4

Thermister inputs (measured with thermisters disconnected).

1 to 8

3 to 4.5 VDC – TE2 (Evaporator Thermister #2)

2 to 9

3 to 4.5 VDC – TC1 (Compartment Thermister #1)

3 to 10

3 to 4.5 VDC – TE1 (Evaporator Thermister #1)

4 to 11

3 to 4.5 VDC – TC3 (Compartment Thermister #3)

5 to 12

3 to 4.5 VDC – TE3 (Evaporator Thermister #3)

6 to 13

3 to 4.5 VDC – TC2 (Compartment Thermister #2)

7 to 14

3 to 4.5 VDC


Compressor Relay

(use E3 – 16 as common for measurements)

Com

115 VAC continuous (power line supply).

NO

115 VAC when compressor is running.

NC

Not

connected.


Alarm wires (check for continuity – these are contact closures only)

Black Common

Red

Normally closed (in no – alarm condition)

White

Normally open (in no – alarm condition)


Display Board
(IDB5D –4330)
E1

Display Board receive

1 +5VDC
2 data

signals

3 ground


E2

Futaba VFD display data connection


TE = Thermister / Evaporator -- Cut-in (39

°F minimum) for Evaporator Temperature

TC = Thermister / Compartment – Compartment cut-out Temperature.
Thermister Tolerance

± 2 degrees.