Problem possible cause correction, Condenser air / flow, Condenser fan fault – Viking VCWB300 User Manual

Page 21

Advertising
background image

TROUBLESHOOTING GUIDE (con’t)

PROBLEM POSSIBLE CAUSE CORRECTION

A. Warm temperature

b2 Check for continuity across

In all Wine Storage

the motor windings of the

Compartments.

inoperative fan motor (See

pages 14 and 19).

8. Condenser Air / Flow
Condenser Fan Fault
a. Dirty condenser

a. Clean condenser

b. Condenser fan blade

b. Check fan blade. Tighten or

loose or obstructed.

remove obstruction.

c. Fan motor disconnected

c. Check fan motor operation.

or malfunctioning.

and electrical connections.

back to compressor. Check

for 115VAC from compressor

to motor. Reconnect or repair

wires or replace motor if

defective.

9. Compressor Fault
a. Compressor

electrical

a. Check integrity of compressor

components

disconnected electrical components (See page

or malfunctioning.

15 and 16). Check electrical

connections

back

to

control

board. Replace defective com-

ponent or repair wiring. Check

for 115VAC from the control

board. Correct any wiring

problems or replace compressor

components if defective. If no

power

from

control

board.

replace

control

board.

b. Compressor inefficient

b. For Compressor specifications,

electrical

inputs

and

output

(See page 16).

c. Compressor locked

c. (See page 16).


B. Warm Temperature 1. Control Set too Warm

a. Check set-points. Adjust set-

in only one wine

points.

storage compartment. 2. Unit Recently Energized a. Allow time for unit to pull down.

3. Unit Recently Stocked

a. Instruct customer

with Wine.

4. High Room Ambient

a. Instruct customer that unit

performs

best

between

60

°F /

16

°C -- 90°F / 32°C.

22