Installing, Continued – Vanguard Heating Gas Log Heater User Manual

Page 13

Advertising
background image

13

103515

INSTALLING

Continued

Floor Clearances

A. If installing appliance on the floor level, you must maintain the minimum

distance of 14" to combustibles (see Figure 8).

Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level

B. If combustible materials are less than 14" to the fireplace, you must install

appliance at least 5" above the combustible flooring (see Figure 9).

Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring

If your installation does not meet the above minimum clearances, you must:
• operate the logs only with the flue damper open, OR
• raise the mantel to an acceptable height, OR
• remove the mantel.

Figure 7 - Minimum Mantel Clearances When Using Hood

Continued

Minimum Non-
Combustible
Material

8"
Min.

12"

15"

18"

All minimum
distances are
in inches

Log Sets
18", 24", and
30" Models

20"

2

1

/2

"

6"

8"

10"

12"

Distances to
Underside of
Mantel

Hood
(GA6050, GA6052)

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

14"
Min.

Combustible
Material

Non-Combustible Material

Hearth

5"
Min.

Combustible
Material