Chimney connections continued – Vogelzang International PB65XL User Manual

Page 9

Advertising
background image

VGZ-003 / 20120327.0

www.vogelzang.com

PB65XL /

Page 9

CHIMNEY CONNECTIONS continued …

e n d o r s e m e n t s f r o m n a t i o n a l l y r e c o g n i ze d
organizations for use as fireplaces, they have not been
tested for connection to wood stove heaters. Connecting
a stove to such a device will void the manufacturer’s
warranty.

Venting a stove directly into a fireplace does not

meet code and should not be attempted. The stove war-
ranty will be void with such an installation. Do not create
a hazard in your home by connecting in this manner.

FIREPLACE INSTALLATION

Directly connecting the stovepipe into the existing

masonry chimney (figure 13 “Type A” Fireplace Conver-
sion) of the fireplace is the only approved method of
installation. This is a complicated and involved process
and to insure safety should only by done by a qualified
installer.
1. An entry hole must be cut through the masonry and

tile liner with minimal damage to the liner. At least 8”
of liner must remain below the entry position. When
locating the stove and stovepipe, all minimum clear-
ances must be observed from combustible surfaces
including mantels, combustible trim work, ceilings
and walls. Positioning the center of the stove pipe
entry into the chimney 24˝ below the ceiling should
insure proper clearance for a 6˝ stovepipe.

2. Install a metal or fire clay (5/8˝ minimum thickness)

thimble. Make sure the thimble is flush with the inner
surface of the chimney liner and does not protrude
into the flue (see figure 8 on page 6).

3. Secure the thimble with refractory mortar. The

thimble should be surrounded by 12˝ of solid unit
masonry brickwork or 24˝ of stone.

4. Install the stovepipe into the thimble as far as pos-

sible without extending past the flue lining (see
figures 8 & 9 on pages 6 & 7).

Fig. 13 - Fireplace Conversion

5. A small airspace (about 1/2”) should remain

between the stovepipe and thimble to allow for
expansion of the pipe. Seal this airspace with high-
temperature caulking or ceramic wool.

6. Secure and seal the damper in the closed posi-

tion using high-temp caulking, ceramic wool, or
furnace cement. Also check to see if the chimney
has a cleanout. If it does, make sure it is closed and
sealed as well. A leaky cleanout will greatly reduce
draft efficiency.

If you have any questions regarding venting your

stove, contact the manufacturer or contact the Na-
tional Fire Protection Association (NFPA) and request
a copy of the latest editions of NFPA Standard 211
and NFPA Standard 908. Their address is:

Battery March Park, Quincy, MA 02269.

Advertising