Unvented propane/lp gas fireplace, Installation, Continued – Vanguard Heating VSGF28PTC User Manual

Page 12: Checking gas connections

Advertising
background image

12

107156

UNVENTED PROPANE/LP GAS FIREPLACE

®

For more information, visit www.desatech.com

Equipment Shutoff Valve

Propane/LP
Supply Tank

INSTALLATION

Continued

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 21).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

3.

Check all joints from propane/LP sup-
ply to equipment shutoff valve (see Fig-
ure 22). Apply noncorrosive leak detec-
tion fluid to all joints. Bubbles forming
show a leak.

4.

Correct all leaks at once.

Figure 21 - Equipment Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Equipment
Shutoff
Valve

Figure 22 - Checking Gas Joints

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect fireplace with its appliance
main gas valve (control valve) and
equipment shutoff valve from gas sup-
ply pipping. Pressures in excess of 1/2
psig will damage fireplace gas regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was con-
nected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

4.

Check all joints of gas supply piping
system. Apply noncorrosive leak detec-
tion fluid to all joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

CHECKING GAS
CONNECTIONS

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a
noncorrosive leak detection fluid
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.

Pressure Testing Fireplace Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 21).

2.

Open propane/LP supply tank valve.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 22). Apply noncorrosive leak de-
tection fluid to all joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Light fireplace (see Operating Fire-
place
, pages 14 through 17). Check all
other internal joints for leaks.

7.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 15 [thermostat-con-
trolled models] or page 16 [manually-
controlled models]).

Gas Control Valve