Specifications, Caution ! warning, Installation – White Rodgers 50M56U-843 User Manual

Page 2

Advertising
background image

2

SPECIFICATIONS

MOUNTING AND WIRING

All wiring should be installed by a qualified heating and air
conditioning contractor or licensed electrician, according to
local and national electrical codes and ordinances.
The control must be secured to an area that will experience a
minimum of vibration and remain below the maximum ambient
temperature rating of 176°F. The control is approved for
minimum ambient temperatures of -40°F.
When mounting the control, any orientation is acceptable.
Choose a location that will not damage, obstruct or place
stress on the control’s terminations, system wiring harness or
system components. After finding a suitable location, drill four
(4) 1/8” holes for mounting control. To ensure proper mounting
hole locations, use the control as a template. When drilling
the holes, take care so that the transformer, wiring harness or
other system components are not damaged. Four (4) #8 sheet
metal screws are provided to complete the installation.
Refer to the wiring diagram and wiring table when connecting
the 50M56U-843 control to other components of the system.
UL approved, 105°C rated 18 gauge, stranded, 2/64” thick
insulation wire is recommended for all low voltage safety circuit
connections.
UL approved 105°C rated 16 gauge min., stranded, 4/64”
thick insulation wire is recommended for all line voltage
connections.
After installation or replacement, follow appliance manufacturer’s
recommended installation or service instructions to ensure
proper operation.

ELECTRICAL RATINGS [@ 77°F (25°C)]:

Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp

Relay Load Ratings:
Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz (resistive)
Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC
Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC

Flame Current Requirements:

Minimum current to insure flame detection: 1 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms

*Measured with a DC microammeter in the flame probe lead
OPERATING TEMPERATURE RANGE:

-40° to 176°F (-40° to 80°C)

HUMIDITY RANGE:

MOUNTING:

Surface mount multipoise

Timing Specs: (@ 60 Hz)

maximum

Flame Establishing Time:

0.8 sec

Flame Failure Response Time:

2.0 sec

Gases Approved: Natural, Manufactured, Mixed, Liquified
Petroleum, and LP Gas Air Mixtures are all approved for use.

TIMING SPECIFICATIONS

(All times are in seconds, unless noted otherwise

50M56U-843

Pre-Purge

30

Initial Ignitor Warm-Up
(1st 64 attempts)

17

Maximum Ignitor Warm-Up

19

Ignition Activation Period

2

Trial for Ignition Period

4

Retries

2

Recycles

3

Valve Sequence Period

12

Interpurge

60

Post-Purge

25

Lockout Time

275

Heat Delay-To-Fan-On

30

Heat Delay-To-Fan-Off

100/150*

Cool Delay-To-Fan-On

6

Cool Delay-To-Fan-Off

45

Auto Reset

60 minutes

*These times will vary depending on option switch

position. See OPERATION section for further infor-
mation.

Do not short out terminals on gas valve or primary
control. Short or incorrect wiring may damage the
thermostat.

CAUTION

!

WARNING

!

FIRE HAZARD

• Do not exceed the specified voltage.
• Replace existing control with exact model and

dash number.

• Protect the control from direct contact with water

(dripping, spraying, rain, etc.).

• If the control has been in direct contact with

water, replace the control.

• Label all wires before disconnection when serv-

icing controls. Wiring errors can cause improper
and dangerous operation.

• Route and secure wiring away from flame.

SHOCK HAZARD

• Disconnect electric power before servicing.
• Ensure proper earth grounding of appliance.
• Ensure proper connection of line neutral and line

hot wires.

EXPLOSION HAZARD

• Shut off main gas to appliance until installation

is complete.

INSTALLATION