White Rodgers 1F80-71 User Manual

Page 4

Advertising
background image

4

CHECK THERMOSTAT OPERATION

If at any time during testing, your system does not operate
properly, contact a qualified serviceperson.

Fan Operation

1. Turn on power to the system.

2. Press SYSTEM button until the system is OFF.

3. Move FAN switch to ON. The blower should begin to operate.

4. Move FAN switch to AUTO position. The blower should stop

within a short period of time.

Heating System

1. Press SYSTEM button until HEAT is displayed. If the heating

system has a standing pilot, be sure to light it.

2. Press

to adjust thermostat setting above room tempera-

ture. The heating system should begin to operate.

3. Press

to adjust temperature setting below room tem-

perature. The heating system should stop operating.

Cooling System

This thermostat has a built-in short-term (5-minute) time delay.
This feature is activated after the compressor shuts down and
the setpoint is changed within the 5-minute period. During this
5-minute period, COOL will flash on the display indicating that
the thermostat has locked out the compressor to allow head
pressure to stabilize. This thermostat does not sense AC power
loss and therefore does not activate the short term compressor
protection feature when power is restored.

To prevent compressor and/or property damage, if the
outdoor temperature is below 50

°

F, DO NOT operate

the cooling system.

1. Press SYSTEM button until COOL is displayed.

2. Press

to adjust thermostat setting below room tempera-

ture. The blower should come on immediately on high speed,
followed by cold air circulation

3. Press

to adjust temperature setting above room tem-

perature. The cooling system should stop operating.

NOTE

CAUTION

!

LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS FEA-
TURE DUE TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL INJURY.

COMPRESSOR SHORT TERM

CYCLE PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature

while testing thermostat operation, simply press

and

buttons at the same time.

DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.