Wiring connections, Warning, Installation – White Rodgers 1F97-1271 User Manual

Page 2: Battery location, Remove old thermostat, Installing new thermostat

Advertising
background image

2

Mounting

Hole

Mounting

Hole

Place Level

across Mounting Tabs

(for appearance only)

Place Level

across Mounting Tabs

(for appearance only)

RC

C

G

W

RH

CLASS II

TRANSFORMER

COOLING

HOT

24VAC

NEUTRAL

LINE IN

Y

L

O

B

Optional (Heat Pump)

Malfunction Indicator

Low

Voltage
System

Power

Optional

Common

Connection

Fan

Relay

Heat

Relay

LINE IN

HOT

24VAC

NEUTRAL

CLASS II

TRANSFORMER

HEATING

Changeover

Valve Cooling

Changeover

Valve Heating

Compressor

Contactor

System

Malfunction

Switch

Remove

Jumper

2 "AA" Batteries

WIRING CONNECTIONS

Refer to equipment manufacturers' instructions for specific
system wiring information. After wiring, see CONFIGURA-
TION section for proper thermostat configuration.

Wiring diagrams shown are for typical systems and describe
the thermostat terminal functions.

WARNING

!

Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.

INSTALLATION

Battery Location

2 "AA" alkaline batteries are included in the thermostat at
the factory with a battery tag to prevent power drainage.
Remove the battery tag to engage the batteries.
To replace batteries, set system to

OFF, remove thermostat

from wall and install the batteries in the rear along the top of
the thermostat (see Figure 1).

Figure 1 – Thermostat base and rear view of thermostat

Remove Old Thermostat

A standard heat/cool thermostat consists of three basic parts:
1. The cover, which may be either a snap-on or hinge type.
2. The base, which is removed by loosening all captive screws.
3. The switching subbase, which is removed by unscrewing

the mounting screws that hold it on the wall or adapter
plate.

Before removing wires from old thermostat,

label each wire with the terminal designation from
which it was attached
. Disconnect the wires from the old
thermostat one at a time.

Do not let wires fall back into

the wall.

Installing New Thermostat

1. Pull the thermostat body off the thermostat base. Forcing

or prying on the thermostat will cause damage to the unit.

2. Place base over hole in wall and mark mounting hole

locations on wall using base as a template.

3. Move base out of the way. Drill mounting holes. If you

are using existing mounting holes and the holes drilled
are too large and do not allow you to tighten base snug-
ly, use plastic screw anchors to secure the base.

4. Fasten base snugly to wall using mounting holes shown

in Figure 1 and two mounting screws. Leveling is for
appearance only and will not affect thermostat operation.

5. Connect wires to terminal block on base using

appropriate wiring schematic (see Figures 2 & 3).

Figure 2 –

Two Transformer System

Figure 3 – Single Transformer System

Terminal Designation

Description

W . . . . . . . . . Heat Relay

G . . . . . . . . . Fan Relay

RH . . . . . . . . . Power for Heating
RC . . . . . . . . . Power for Cooling

C . . . . . . . . . Common wire from secondary side of cooling

system transformer or heat only system transformer

2

Terminal Designation

Description

L . . . . . . . . . . Heat pump malfunction indicator for

systems with malfunction connection

O . . . . . . . . . Changeover valve for heat pump energized

constantly in cooling

B . . . . . . . . . Changeover valve for heat pump energized

constantly in heating

Y . . . . . . . . . Compressor Relay

Optional 24VAC

Common

Connection

RC

C

G

W

RH

CLASS II

TRANSFORMER

24 Volt

Hot

24 Volt

Common

LINE IN

Y

L

O

B

Optional (Heat Pump)

Malfunction Indicator

Fan

Relay

Heat

Relay

System

Malfunction

Switch

Single transformer heat and cool
systems require a jumper from
RC to RH for heat only systems.
Attach power to RH. For cool only
attach power to RC.

*

Low

Voltage
System

Power

Changeover

Energized in Cooling

Changeover

Energized in Heating

Compressor

Relay

*

6. Push excess wire into wall and plug hole with a fire re-

sistant material (such as fiberglass insulation) to prevent
drafts from affecting thermostat operation.

7. Carefully line the thermostat up with the base and snap

into place.

TERMINAL DESIGNATION DESCRIPTIONS

NOTE: If continuous backlight or hardwired power
input are desired but do not function in both HEAT
and COOL modes, cut the heating transformer 24V
wires and tape off. Connect the neutral circuit
disconnected from the heating transformer to the
neutral circuit of the cooling transformer. Disconnect
the wire to the RH terminal and install a jumper
between

RH and RC. Depending on the system

requirements, replace the cooling transformer with a
75VA class II transformer if needed.

NOTE: Heat Pump without Aux: If using L for MALF indicator, C
must be connected. Terminals

W and Y must be jumpered and CR

HEAT must be selected to SL in Configuration Menu item 6.