— User’s Information Manual

8

Maintenance procedures — END OF SEASON

Maintenance procedures — EVERY 6 MONTHS

Follow “TO TURN OFF GAS TO APPLIANCE” on page 9

1.

of this manual.

Do not drain system unless exposure to freezing temperatures

2.

will occur.

Do not drain the system if it is filled with an antifreeze

3.

solution.

DO NOT shut down boilers used for domestic water heating.

4.

They must operate year-round.

Check the boiler piping

Remove boiler front access door and perform gas leak inspection per

1.

steps 1 through 7, Operating Instructions, page 9. If gas odor or leak

is detected, immediately shut down boiler following procedures on

page 9. Call a qualified service technician.

Visually inspect for leaks around internal water piping. Also inspect

2.

external water piping, circulators, relief valve and fittings. Immediately

call a qualified service technician to repair any leaks.

Have leaks fixed at once by a qualified service technician.

Failure to comply could result in severe personal injury, death

or substantial property damage.

Operate relief valve

Reinstall door securely after inspections.

1.

Reinstall the jacket front door after servicing. The boiler front

door must be securely fastened to the boiler to prevent boiler

from drawing air from inside the boiler room. This is par-

ticularly important if the boiler is located in the same room

as other appliances. Failure to keep the door securely fastened

could result in severe personal injury or death. Contact your

installer or technician immediately if the front door does not

correctly in place or if the door gaskets are damaged.

Before proceeding, verify that the relief valve outlet has been piped

2.

to a safe place of discharge, avoiding any possibility of scalding from

hot water.

To avoid water damage or scalding due

to valve operation, a metal discharge

line must be connected to relief valve

outlet and run to a safe place of disposal.

This discharge line must be installed by

a qualified heating installer or service

technician in accordance with the in-

structions in the Ultra Boiler Manual.

The discharge line must be terminated

so as to eliminate possibility of severe

burns or property damage should the

valve discharge.

Read the boiler pressure/temperature gauge to

3.

make sure the system is pressurized. Lift the relief

valve top lever slightly, allowing water to relieve

through the valve and discharge piping.

If water flows freely, release the lever and allow the

4.

valve to seat. Watch the end of the relief valve dis-

charge pipe to ensure that the valve does not weep

after the line has had time to drain. If the valve

weeps, lift the seat again to attempt to clean the

valve seat. If the valve continues to weep afterwards,

contact your qualified service technician to inspect

the valve and system.

If water does not flow from the valve when you

5.

lift the lever completely, the valve or discharge line

may be blocked. Immediately shut down the boiler,

following the operating instructions on page 9. Call

your qualified service technician to inspect the

boiler and system.