If you have a single stage compressor system see the dia-
gram below. A relay (customer provided) should be installed
as shown in Fig 7 to switch the fan speed to the next lower
speed on a call for dehumidification from the thermostat. The
reduction in air flow allows the coil to remove more humidity
from the air. The relay should be rated for blower motor load.
Since this configuration reduces the air flow in cooling, the

WIRING DIAGRAMS

anti-freeze-up control (White-Rodgers CAFC) or equivalent is
recommended. The CAFC prevents the air conditioning coil
from freezing due to low air flow, dirty filters, low refrigerant
pressure, etc. The CAFC snaps onto the suction line close to
the evaporator coil as possible and breaks the compressor
circuit when the suction line drops below 38 °F and re-make
the circuit at 46°F.

HOT

NEUTRAL

120 VAC

24 VAC

Relay
90-290Q
or equivalent

HOT

NEUTRAL 120 VAC

TRANSFORMER

R

HM

Humidifier

System

Figure 6 – Typical Wiring for 120V Humidifier System

HOT

NEUTRAL 120 VAC

TRANSFORMER

HM

24 VAC

Humidifier

System

R

Figure 7 – Typical Wiring for 24V Humidifier System

Dehumidification wiring without an electronically controlled variable speed blower system for

single stage compressor system only.

HM

DHM

Humidification Terminal,

Energizes on call for

heat if Humidity setpoint

is above room humidity.

Can also be used to

provide humidification

independent of a call for

heat and/or in cooling

mode if Automatic

Humidification is

selected in Configura-

tion Menu item #34

De-energizes on call for

Dehumidification to

lower the fan speed.

The DHM terminal is

only used on systems

with a compatible

dehumidification feature

that have the required

terminal connection on

the contol module or

have a relay installed to

lower the fan speed

+

S

-

Supply voltage

to remote

temperature

sensor

Remote

temperature

sensor signal

Supply voltage

to remote

temperature

sensor

Figure 4 – Humidity and Sensors

Relay
90-293Q
or equivalent

No

NC

“Heat Fan Output”

N

Dehum

Speed Fan

Med

DHM

N

Low

Normal High

“Cool Fan Output”

1

2

Normal Cool speed position (DHM energized)
Dehum speed mode (DHM de-energized)

1

2

Figure 5 – Typical Wiring for Dehumidifier System