Installation, Wiring diagram, Energy management recovery (emr) – White Rodgers 1F82-0261 User Manual

Page 3

Advertising
background image

3

INSTALLATION

batteries should be replaced before leaving. When less than
two months of battery life remain, the setpoint temperature will
offset by 10 degrees (10 degrees cooler in Heat mode / 10
degrees warmer in Cool mode). If offset occurs, the normal
setpoint can be manually reset with

or

. Another offset

will occur within two days if batteries are not replaced. To
replace the batteries, set system to OFF.

ENERGY MANAGEMENT RECOVERY

(EMR)

When the Energy Management Recovery (EMR) feature is
activated the thermostat will start the program early to achieve
the programmed temperature setting by the time specified in
the program and minimize Auxiliary Heat use. Heat Pump and
Cooling systems start approximately 15 minutes early for every
1° of temperature (gas or electric heat starts 5 minutes early
for every 1°) required to reach the next temperature setting.
This helps the building warm up in Heating or cool down in
Cooling so it reaches the program temperature right on time.

EMR – Heat Pump Example:
If the thermostat is programmed to an overnight heating
temperature of 66°F, and the next program period, beginning at
6:00 AM is programmed to 70°F, the thermostat will automatically
advance the program setting and start the heating system at
about 5:00 AM. The thermostat will use Heat Pump only during
the majority of the recovery period. It will use Auxiliary Heat
only if the thermostat calculates the Heat Pump will not meet
setpoint by the programmed time. This saves money by using
the Heat Pump for setback recovery as much as possible and
using Auxiliary Heat only if the Heat Pump cannot recover by
the time programmed.
To turn EMR off, use the Configuration Menu on page 5. When
EMR is set to

OFF the temperature settings will change at

exactly your program times.

WIRING DIAGRAM

L

R

C

24 VAC

120 VAC

Hot

SYSTEM

MONITOR

SWITCH

Neutral

THERMOSTAT

SYSTEM

G

W2

Figure 2. Typical wiring diagram for single transformer systems

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position
The 24 volt neutral connection to terminal C on the thermostat is not required if you

replace the batteries once a year with fresh “AA” alkaline batteries.

Aux/Emergency

Heat Relay

(Stage 2)

Fan

Relay

The 24 volt neutral connection
to terminal C on thermostat is
not required if you replace the
batteries once a year with
fresh “AA” alkaline batteries.

NOTE

**

*

**

Advertising