Figure 29

Steam boiler application
Domestic water heating using
water pumped from steam boiler

• Locate

flow/check valve as

close as possible to water

heater boiler side connections

— to reduce heat loss between

cycles.

1. These drawings are conceptual only. They show representative piping components and

layout. Weil-McLain does not represent that the drawings meet any particular mechanical

or building codes. The installer is responsible for inclusion of all required safety devices, or

other miscellaneous piping hardware not shown on drawings. The installer is responsible

for proper sizing/selection of all hardware shown on this diagram.

2. See Weil-McLain installation instructions for specific details on installing the boiler.

Notes

C

Boiler-side piping

(except

Gas)

continued

Use ball valve  to blend some of

the water returning to the boiler

with the hot water coming from the

boiler. This will reduce the possibil-

ity of flashing (cavitation) in the

circulator. Slowly open valve  until

temperature gauge 8 reads 200°F.
Lock or remove the handle from

valve  after adjusting.