Pre-installation, Manual, Operating restrictions – Weil-McLain PLUS LINE PLUS-E017-A/1206 User Manual

Page 7: Code restrictions

Advertising
background image

Part Number PLUS-E017-A/1206



Manual

• Installation • Start-Up • Usage • Maintenance • Parts

Operating

restrictions

• Maximum domestic hot water temperature (

Use only for special high-temperature

operational requirements

):

10°F for GOLD Plus 0/0/0/80 or

Plus 0/0/80.

190°F for PLUS 100/110/119.

• Maximum boiler water temperature — 210°F.
• Maximum working pressure for inner (domestic water) tank — 10 psig.
• Maximum working pressure for outer (boiler water) tank —  psig.
• pH and chloride limits for water heaters are:

• chloride — less than 80 mg/l.
• pH — above  and less than 8.

Code restrictions

National Standard Plumbing Code
Single wall heat exchanger in water heater complies with National Standard Plumbing Code,

provided that:
• boiler water (including additives) is practically non-toxic, having toxicity rating or class

of 1, as listed in Clinical Toxicology of Commercial Products, and

• boiler water pressure is limited to maximum 0 psig by approved relief valve.

Uniform Plumbing Code
Single-wall heat exchangers are permitted if they satisfy all of the following requirements —
1. The heat transfer medium is potable water or contains only substances which are recognized

as safe by the U. S. Food and Drug Administration.

2. The pressure of the heat transfer medium is maintained less than the normal minimum

operating pressure of the potable water system.

Exception: Steam complying with #1, above.

. The equipment is permanently labeled to indicate that only additives recognized as safe

by the FDA shall be used in the heat transfer medium.

Other heat exchanger designs may be permitted where approved by the Administrative

Authority.

A1

Pre-installation

continued