Important Safety Requirements

This cooker must be installed in accordance with the
IEE Wiring Regulations (Current Edition).
Detailed recommendations are contained in the
following British Standards Codes Of Practice: B.S.
6172/ B.S. 5440, Par. 2 and B.S. 6891 Current
Editions.

Provision for Ventilation

The room containing the cooker should have an air
supply in accordance with B.S. 5440: Part 2: Current
Editions.

The following requirements for ventilation must be
met.

The cooker should not be installed in a bed sitting
room with a volume of less than 20m

3

, if it is

installed in a room of volume less 5m

3

an air vent of

effective area of 110cm

2

is required; if it is installed

in a room of volume between 5m

3

and 10m

3

, an air

vent of effective area 50cm

2

is required, while if the

volume exceeds 11m

3

no air vent is required.

However, if the room has a door which opens
directly to the outside, no air vent is required even
when the volume is between 5m

3

and 11m

3

.

If there are other fuel burning appliances in the same
room, B.S. 5440: Part. 2: Current Editions should be
consulted to determine the requisite air vent
requirements.