Selection data – York STYLE A YCWS User Manual

Page 12

Advertising
background image

12

YORK INTERNATIONAL

GUIDE TO SELECTION

Complete water chilling capacity ratings for YORK YCWS
chillers are shown on the following pages to cover the
majority of job requirements. For any application be-
yond the scope of this Engineering Guide, consult your
nearest YORK Office.

SELECTION RULES

1. RATINGS - YCWS 200, 230 380, 460 & 575-3-60 rat-

ing are certified in accordance with ARI standard 550/
590, at the ARI standard condition. Rating not at stan-
dard ARI conditions are rated in accordance with ARI
rating procedures. These ratings may be interpolated
but should not be extrapolated.

2. COOLING WATER QUANTITY - Ratings are based

on 10ºF chilled water range. Use the chilled water
correction factors (below) for other ranges except as
limited by water pressure drop, minimum or maximum
water flows for the cooler.

3. CONDENSER WATER QUANTITY – Rating are ap-

plicable from 2 to 4 gpm/ton as limited by water pres-
sure drop or minimum or maximum water flows for
the condenser. Using the tabulated MBH, the Cond.
GPM is calculated as follows:

Cond. GPM =

MBH x 2

Cond. Water Range (ºF)

4. FOULING FACTORS – Rating are based on 0.0001

evaporator and 0.00025 condenser fouling factor. For
other fouling factors, consult the table below or con-
tact your YORK representative.

EVAP FOULING FACTORS

0.0001

x

0.00025

6

0.9692

1.0015

0.9972

1.0001

8

0.9849

1.0008

0.9980

1.0001

10

1.0000

1.0000

0.9982

1.0001

12

1.0133

0.9993

0.9978

1.0001

14

1.0248

0.9986

0.9979

1.0001

Note: Temperature split factors @ 44ºF Leaving Chilled Liquid Temp

(LCLT)

Selection Data

COND FOULING FACTORS

0.00025

x

0.0005

8

0.9998

1.0004

0.9957

1.0072

10

1.0000

1.0000

0.9959

1.0068

12

1.0001

0.9998

0.9961

1.0065

14

1.0001

0.9998

0.9965

1.0060

Note: Temperature split factors @ 95ºF Leaving Condenser Water
Temp (LCWT).

METHOD OF SELECTION
If the duty requires a 10ºF range on both the cooler and
condenser, see “Ratings”. For water ranges other than
10ºF, use the following procedure.

1. Determine capacity required from the following for-

mula

GPM x Chilled Water Range (ºF)

Capacity (tons) =

24

2. After applying any fouling factor corrections, the ac-

tual condenser heat rejection may be determined as
follows:

Heat Rejection (Btuh) = (Tons x 12,000) + (kW x 3415)

Heat Rejection (Btuh)

Heat Rejection (MBH) =

1000

= (Tons x 12) = (kW x 3.415)

3. Determine condensing water requirements for water

cooled models as follows:

Heat Rejection (MBH) x 1000

Condenser Tons =

15,000

Condenser Tons x 30

Cond. Water GPM =

Condenser Water Range (ºF)

Or combine the two formulas:

MBH x 2

Cond. Water GPM =

Condenser Water Range (ºF)

Temp
Split

Tons

Compr

kW

Tons

Compr

kW

Temp
Split

Tons

Compr

kW

Tons

Compr

kW