York STYLE A YCWS User Manual

Page 17

Advertising
background image

FORM 201.24-EG1

17

YORK INTERNATIONAL

NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi= Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.

LEAVING CONDENSER WATER TEMPERATURE (°C)

LCWT

30.0

35.0

40.0

(°C)

KWo

KWi

KW

COP

KWo

KWi

KW

COP

KWo

KWi

KW

COP

YCWS0200SC

YCWS0220SC

YCWS0240SC

5.0 632.7

111.7

744.0

5.7

599.6

125.6

725.0

4.8

567.2

140.4

707.0

4.0

6.0 657.1

111.8

768.0

5.9

623.4

125.9

749.0

5.0

589.0

140.7

729.0

4.2

7.0 681.1

111.8

792.0

6.1

646.6

126.1

772.0

5.1

609.7

141.0

750.0

4.3

8.0 705.4

111.7

817.0

6.3

668.4

126.3

794.0

5.3

632.8

141.3

774.0

4.5

9.0 730.4

111.5

842.0

6.6

694.6

126.4

821.0

5.5

657.8

141.6

799.0

4.6

10.0 756.0

111.3

867.0

6.8

719.3

126.5

845.0

5.7

681.8

141.9

823.0

4.8

5.0 690.4

123.1

813.0

5.6

654.5

138.3

792.0

4.7

617.7

154.5

772.0

4.0

6.0 714.3

123.2

837.0

5.8

679.1

138.6

817.0

4.9

641.4

154.9

796.0

4.1

7.0 741.9

123.2

865.0

6.0

704.3

138.9

843.0

5.1

664.2

155.2

819.0

4.3

8.0 768.6

123.2

891.0

6.2

730.1

139.2

869.0

5.3

690.2

155.6

845.0

4.4

9.0 795.9

123.1

919.0

6.5

756.5

139.4

896.0

5.4

716.4

156.0

872.0

4.6

10.0 823.9

122.8

946.0

6.7

783.6

139.5

923.0

5.6

742.5

156.4

898.0

4.8

5.0 745.5

134.7

880.0

5.5

706.5

151.2

857.0

4.7

666.6

168.9

835.0

4.0

6.0 772.8

134.9

907.0

5.7

733.1

151.6

884.0

4.8

692.3

169.3

861.0

4.1

7.0 800.9

134.9

935.0

5.9

760.4

152.0

912.0

5.0

718.6

169.7

888.0

4.2

8.0 829.6

134.9

964.0

6.2

788.2

152.3

940.0

5.2

745.6

170.2

915.0

4.4

9.0 859.0

134.8

993.0

6.4

816.6

152.5

969.0

5.4

773.2

170.6

943.0

4.5

10.0 897.9

134.5

1032.0

6.7

845.7

152.7

998.0

5.5

801.3

171.0

972.0

4.7

Advertising