Incoming wire range selections, Cont.) – York STYLE A YCWS User Manual

Page 40

Advertising
background image

40

YORK INTERNATIONAL

Incoming Wire Range Selections

(Cont.)

MULTIPOINT WIRING SYSTEM #1

YCWS0100SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

YCWS0120SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0140SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0180SC -17 #2/0 - 500 KCM

# 4 - 3/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0200SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

# 8 - 350 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0220SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0240SC

(2) #2 - 4/0 AWG (2) # 6 - 1/0 AWG

(2) #3/0 - 250 KCM

# 4 - 3/0 AWG

(3) 2/0 - 400 KCM

(2) # 2 - 4/0 AWG

YCWS0100SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0120SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0140SC

#2 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 4 - 3/0 AWG

YCWS0180SC -28

#2 - 300 KCM

# 6 - 1/0 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0200SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0220SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0240SC

#2/0 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

250 - 500 KCM

# 4 - 3/0 AWG

YCWS0100SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0120SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0140SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0180SC -40

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0200SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0220SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0240SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

#6 - 350 KCM

# 6 - 1/0 AWG

YCWS0100SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

YCWS0120SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

YCWS0140SC

#6 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0180SC -46

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0200SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0220SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0240SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 6 - 1/0 AWG

YCWS0100SC

#18 - 2 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

YCWS0120SC

#18 - 2 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

YCWS0140SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#2 - 4/0 AWG

# 8 - 2 AWG

YCWS0180SC -58

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#2 - 4/0 AWG

# 8 - 2 AWG

YCWS0200SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0220SC

#6 - 1/0 AWG

# 8 - 2 AWG

#14 - 1/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

YCWS0240SC

#2 - 4/0 AWG

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

#4 - 300 KCM

# 8 - 2 AWG

CHILLER

MODEL

VOLT
CODE

TERM

BLK

TERMINAL BLK

CUSTOMER

GROUND

N-F DIS

SW

N-F DIS SW

CUSTOMER

GROUND

CKT.BRKR

CKT.BRKER

CUSTOMER

GROUND

NOTES:

(for Electrical Data on pages 26-28)

1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of

the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory

Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -50, add 5 amps;

2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included

in the circuit, per N.E.C. Article 440.

3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated

load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It
is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or opera-
tion at ambient temperatures in excess of 35ºC (95ºF) is anticipated.

4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated

load amps for all other loads included in the circuit, per N.E.C. Article 440-22.