York STYLE A YCWS User Manual
Page 35

FORM 201.24-EG1
35
YORK INTERNATIONAL
NOTES:
1. CLEARANCES - Recommended YORK clearances
to service the unit are as follows:
Rear to Wall:
508mm
Front to Wall:
813mm
Top:
508mm
Tube cleaning and removal:
2438mm (either end)
2. Shipping skids (not shown) will increase the height
of the unit by 152mm, but MUST be removed upon
installation.
3. Spring and neoprene isolators will increase the over-
all height of the unit by approximately 76mm.
REF NO
YCWS0100
YCWS0120
YCWS0140
YCWS0180
YCWS0200
YCWS0220
YCWS0240
A
3527
3527
3527
4775
4775
4775
4775
B
1715
1715
1715
2316
2316
2316
2316
C
953
953
953
1556
1556
1556
1556
D
1524
1524
1524
1524
1524
1524
1524
E
905
905
905
994
994
994
994
F
1459
1459
1459
2069
2069
2069
2069
G
1459
1459
1459
2069
2069
2069
2069
H
1169
1169
1169
1722
1722
1722
1722
I
1169
1169
1169
1722
1722
1722
1722
J
156
156
156
130
130
130
130
K
210
210
210
229
229
229
229
L
210
210
210
251
251
251
251
M
1829
1893
1893
2010
2010
2010
2010
N
1033
1033
1033
1085
1085
1085
1085
O
601
601
601
613
613
613
613
P
254
254
254
254
254
254
254
Q
708
708
708
837
837
837
837
R
1038
1038
1038
1038
1038
1038
1038
S
864
864
864
914
914
914
914
T
432
432
432
457
457
457
457
U
406
406
406
422
422
422
422
V
127
127
127
152
152
152
152
W
203
203
203
203
203
203
203
X
337
337
337
362
362
362
362
REVISED DIMENSIONS FOR 200/230V CHILLERS
REF
YCWS0100
YCWS0120
YCWS0140
YCWS0180
YCWS0200
YCWS0220
YCWS0240
C
819
819
819
1422
1422
1422
1422
D
1791
1791
1791
1791
1791
1791
1791
Q
530
530
530
659
659
659
659
R
1219
1219
1219
1219
1219
1219
1219