FORM 100.50-EG5 (108)

25

JOHNSON CONTROLS

Exhaust Fan Data

EXHAUST FAN MOTOR SIZING INSTRUCTIONS

In order to determine the proper exhaust fan motor size, add the return duct static pressure to the appropriate damper
pressure drop value in Table 14 to get the total static pressure applied to the exhaust fan. Based on the exhaust fan
airfl ow and total static pressure, determine the brake horsepower and RPM of the exhaust fan.

TABLE 15 – FORWARD-CURVED FAN

CFM STD.

AIR

Total Static Pressure (inches of water column)

0.3

0.5

0.8

1

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

6000

8000

10000

12000

14000

5.4

645

16000

5

528

5.7

584

6.4

633

7.2

680

18000

6.8

579

7.7

632

8.5

678

9.3

721

20000

9.1

632

10.1

681

11.1

725

12

765

22000

11.8

685

13

731

14.1

772

15.1

811

24000

15.1

739

16.4

782

17.6

821

18.8

858

26000

18.9

794

NOTE: For performance at operating points not included in these tables, consult your local YORK representative.