York ECO HFC-410A User Manual

Page 31

Advertising
background image

FORM 100.50-EG5 (108)

31

JOHNSON CONTROLS

is called from the thermostat, the Supply Fan will start.
Ventilation functions (if equipped) will be permitted to
run with an occupied signal. Economizer functions will
operate with a “G” call and a call for cooling.

HEATING OPERATION

Thermostat Control

If a 7-wire thermostat (2 Cool/2 Heat) controls the unit,
all zone-temperature setpoint-control is maintained at

the thermostat. With this operation, the unit remains idle
until it receives a stage call from the thermostat. If “G”
is called from the thermostat, the Supply Fan will start.
Ventilation functions (if equipped) will be permitted to
run with an occupied signal.

TABLE 22 – POWER-SUPPLY-CONDUCTOR SIZE RANGE

Dual-Point TB

Supply

Voltage

Single-Point

TB

Single-Point

Disconnect

TB 1

TB 2

208V

(2*) 250 kcmil-500 kcmil

(2*) 2 AWG-500 kcmil

6 AWG-400 kcmil

6 AWG-350 kcmil

230V

(2*) 250 kcmil-500 kcmil

(2*) 2 AWG-500 kcmil

6 AWG-400 kcmil

6 AWG-350 kcmil

460V

6 AWG-400 kcmil

6 AWG-350 kcmil

14 AWG-2/0

14 AWG-2/0

575V

6 AWG-400 kcmil

6 AWG-350 kcmil

14 AWG-2/0

14 AWG-2/0

NOTE: 2* = Dual pairs per phase