Unit weights – York ECO HFC-410A User Manual

Page 36

Advertising
background image

JOHNSON CONTROLS

36

FORM 100.50-EG5 (108)

Unit Weights

TABLE 23 – UNIT WEIGHTS

Model

050

051

060

061

Basic Unit*

7433

7433

7800

7819

Economizers

No

Outside

Air

240

240

240

240

25% Outside Air Fixed Position Maual Damper

446

446

446

446

25% Outside Air 2 Position Actuated Damper

476

476

476

476

Full Modulation with Minimum Position

476

476

476

476

Power Exhausts

Fan, Motor, Modulating Damper and Hood

501

501

501

501

Fan, Motor, VFD, Barometric Damper and Hood

506

506

506

506

Gas Heat

375

MBH

162

162

162

162

750

MBH

324

324

324

324

1125 MBH (Bottom Discharge)

486

486

486

486

Options

Open Perimeter Curb

544

544

544

544

Condenser Coil Wire Guard

64

64

64

64

Copper Evaporator Coils (additional)

312

312

416

416

Copper Condenser Coils (additional)

516

516

773

773

12” Rigid Filters (additional)

319

319

319

319

*Unit includes FC fan w/ 20 hp motor, VFD and 2” throwaway fi lters

X

339

Y

92

A

B C

D

Condenser
Coil End

Center of Gravity

TABLE 24 – UNIT CENTER OF GRAVITY

Model

050

051

X

Y

X

Y

Basic Unit

184.1

50.2

184.1

50.2

Basic Unit w/ Econ.

191.0

49.9

191.0

49.9

Basic Unit w/ Econ. & Heating

187.4

50.0

187.4

50.0

Basic Unit w/ Econ. & Heating & Power Exhaust

194.9

49.5

194.9

49.5

Model

060

061

X

Y

X

Y

Basic Unit

179.8

49.9

179.6

50.0

Basic Unit w/ Econ.

186.7

49.7

186.5

49.7

Basic Unit w/ Econ. & Heating

183.5

49.8

183.2

49.8

Basic Unit w/ Econ. & Heating & Power Exhaust

190.9

49.3

190.7

49.3