Table 5: steam coil capacity, mbh@2 psig, Table 6: hot water capacity, mbh, Table 7: pressure drop vs. gpm – York EVAPORATOR BLOWERS K2EU060 User Manual

Page 8: Table 8: capacity correction vs. gpm

Advertising
background image

036-21300-002-A-0905

8

Unitary Products Group

NOTE: Steam rate (lb./hr.) = 1.025 x MBH

CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a steam coil acces-
sory.

NOTE: Water Temperature Drop,

0

F = 2 x MBH

CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a hot water coil accessory.

TABLE 5: STEAM COIL CAPACITY

1

, MBH@2 PSIG

2

STEAM COIL

MODEL

UNIT MODEL

CFM

DRY BULB TEMPERATURE OF AIR ENTERING COIL, ºF

10

30

50

70

1NF0450

060

1600

104.0

94.0

83.9

73.9

2000

115.2

104.0

93.1

81.9

2400

124.9

113.0

100.9

89.0

1NF0451

090

2400

172.2

155.5

139.1

122.4

3000

191.2

172.6

154.3

136.0

3600

207.5

187.1

167.4

147.4

120

3200

196.4

177.6

158.8

140.0

4000

217.3

195.3

175.3

154.8

4800

236.1

212.9

190.4

167.8

1NF0452

180

4800

298.2

268.4

236.7

211.5

6000

329.1

297.0

265.6

234.1

7200

356.4

321.8

287.9

254.0

1. These capacities do not include any blower motor heat.
2. Multiply these capacities by the following factors to correct for higher steam pressures.

Steam Pressure, psig

5

10

15

20

25

Capacity correction factor

1.05

1.12

1.19

1.25

1.30

TABLE 6: HOT WATER CAPACITY

1

, MBH

WATER COIL MODEL

UNIT MODEL

GPM

CFM

ENTERING WATER TEMP. MINUS ENTERING AIR TEMP., ºF

70

90

110

130

150

1HW0450

060

10

1600

46.5

60.4

74.6

89.0

101.8

2000

51.7

67.2

83.0

99.2

113.4

2400

56.0

73.0

90.4

107.9

123.3

1HW0451

090

15

2400

78.0

101.3

124.7

148.5

169.7

3000

87.7

113.3

139.6

166.6

190.4

3600

95.5

124.0

153.0

182.1

208.1

120

15

3200

90.3

117.1

144.6

172.1

196.6

4000

100.2

130.2

160.7

191.3

218.6

4800

108.3

140.9

174.3

207.5

237.4

1HW0452

180

20

4800

135.5

175.1

215.8

257.4

294.1

6000

150.0

195.0

240.3

285.9

326.6

7200

162.4

210.8

260.4

309.8

354.3

1. These capacities do no include any blower motor heat.

TABLE 7: PRESSURE DROP VS. GPM

1HW0450

GPM

10

20

30

Pressure Drop, PSI

.10

.32

.67

1HW0451

GPM

15

30

45

Pressure Drop, PSI

.17

.58

1.22

1HW0452

GPM

20

40

60

Pressure Drop, PSI

.20

.67

1.41

TABLE 8: CAPACITY CORRECTION VS. GPM

1HW0450

GPM

20

30

Capacity Correction

1.12

1.16

1HW0451

GPM

30

45

Capacity Correction

1.11

1.15

1HW0452

GPM

40

60

Capacity Correction

1.12

1.17

Advertising