343615-YTG-B-0308

Johnson Controls Unitary Products

13

TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP

63

77

84

77

84

81

85

79

84

125

71

71

72

73

74

75

71

72

250

57

58

55

56

66

66

60

61

500

53

53

51

51

60

60

55

55

1000

50

50

45

46

60 60 53 53

2000

49

49

43

44

58

58

50 50

4000

49

49

42

43

59

59

47

47

8000

49

49

48

48

54

54

47 47

DY060 / 5 Ton

Horizontal Ducted Inlet

840

845

1166

1188

0.2

0.6

0.3

1.3

1.51

0.80

1695

1100

2618

1323

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

0.67

0.50

Cooling

Operation

2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Octave Center Freq.

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP

63

82

87

79

88

88

89

82

87

125

75

76

72

74

82

83

78

78

250

69

69

66

66

79

79

73

73

500

64

64

60

60

72

72

66

66

1000

59

60

55

56

68

68

61

61

2000

55

55

50

50

65

65

57

57

4000

58

58

52

52

68

68

60

60

8000

55

55

49

49

66

67

56

56

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

0.6

1100

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

DY060 / 5 Ton

Horizontal Ducted Discharge

840

845

1166

1188

0.80

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment .

0.50

0.3

2618

1.51

Cooling

Operation

2

(dB)

0.2

1695

0.67

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

1.3

1323